People Electric · Dust-Proof Junction Box
Product overview
People Electric BHD-DIP junction boxes provide industrial cable or conduit connections in the manufacturer dust-protection product family. This listing covers only the flat-cover A–E entry patterns and the five thread sizes with a matching cable-diameter/dimension row in the original dedicated PDF.
Technical selection summary
| Manufacturer / series | Original People Electric BHD-DIP |
|---|---|
| Offered cover / patterns | Flat cover only:A one entry;B two opposite;C three;D four;E two perpendicular |
| Housing | Die-cast aluminium alloy with protective surface coating |
| Rated current / voltage | 20A;AC380V/220V as manufacturer catalogue; confirm terminal and circuit suitability |
| Manufacturer marking | DIP A20 TA,T4 as original catalogue; verify actual supplied marking and applicable documents |
| Ingress / corrosion protection | IP65 / WF1 as catalogue |
| G1/2 | Cable outside diameter8–10mm;referenceA166/B108/C104/D68mm |
| G3/4 | Cable outside diameter8–14mm;referenceA168/B108/C105/D68mm |
| G1 | Cable outside diameter12–17mm;referenceA170/B108/D68mm;C not specified |
| G1 1/4 | Cable outside diameter13–23mm;referenceA200/B122/D88mm;C not specified |
| G1 1/2 | Cable outside diameter17–26mm;referenceA210/B122/D88mm;C not specified |
Only flat-cover A–E patterns and the displayed five G-thread sizes are selectable. Hung-cover F–J versions and the conflicting G-code ordering example are outside this listing. G2 has no matching dimension/cable row in this source and is not offered here. Confirm actual entry pattern and each thread,cable seals,terminal count,conductor sizes,unused-entry closure and final installation drawing. Catalogue marking is a manufacturer reference; verify actual supplied marking,site suitability and required conformity documentation.
Typical applications
- Cable or conduit junctions in industrial installations using the correctly specified manufacturer dust-protection assembly.
Specify your enquiry
For a focused quotation, include:
- BHD-DIP,flat-cover patternA–E,G-thread size and quantity.
- Terminal/conductor requirements,cable diameters,entry seals and unused-entry closures.
- Site conditions,actual required marking/documents and mounting arrangement.
Download People Electric BHD-DIP catalogue (PDF)