NewTrend · Delayed pulse-output timer relay
Product overview
NewTrend RT6-P1 generates a timed output pulse after an adjustable initial delay. Set the delay t1 and pulse duration t2 independently using their range selectors and fine-adjustment knobs. Linking S-A1 resets the delay sequence. The relay has 1 SPDT output contacts and an 18mm DIN-rail housing.
Technical selection summary
| Model | RT6-P1 |
|---|---|
| Output contacts | 1 SPDT |
| A230 power input | AC maximum 6VA / 1.3W |
| Weight | S240: 53g; A230: 65g |
| Function | Output pulse after an independently adjustable delay |
| Supply terminals | A1-A2 |
| Control supply options | S240: AC/DC 24-240V; A230: AC 230V; 50-60Hz |
| Supply tolerance | -15% to +10% |
| S240 burden | AC 0.7-3VA / DC 0.5-1.7W |
| Supply indication | Green LED |
| Time setting | Independent t1/t2 range selectors and 10%-100% potentiometers |
| Timing scales | 0.1s-100days; independent t1 and t2 |
| Marked time ranges | 1s, 10s, 1min, 10min, 1h, 10h, 1day, 10days, 30days, 100days |
| Time setting deviation | 10% with mechanical adjustment |
| Repeat accuracy | 0.2% of set value |
| Temperature coefficient | 0.05%/degree C at 20 degrees C |
| Contact rating | 10A (AC-1) |
| Switching voltage | 250VAC / 24VDC |
| Minimum DC breaking power | 500mW |
| Output indication | Red LED |
| Mechanical life | 10,000,000 operations |
| Electrical life (AC-1) | 100,000 operations |
| Reset time | Maximum 200ms |
| Operating temperature | -20 to +55 degrees C |
| Storage temperature | -35 to +75 degrees C |
| Mounting | DIN rail to EN/IEC 60715 |
| Protection | IP40 front panel; IP20 terminals |
| Operating position | Any |
| Overvoltage category | III |
| Pollution degree | 2 |
| Maximum conductor size | Solid: 1 x 2.5mm2 or 2 x 1.5mm2; with sleeve: 1 x 2.5mm2 (AWG 12) |
| Terminal tightening torque | 0.4Nm |
| Body dimensions | 90 x 18 x 64mm |
| Referenced standards | EN 61812-1; IEC 60947-5-1 |
Set the initial delay t1 and the output pulse duration t2 separately. Use the S-A1 input to reset timing as shown in the connection and timing diagrams.
Operation
- After the supply is applied, the relay waits for t1, then operates its output contacts for t2 before they return to their rest state.
- Shorting S-A1 resets the delay sequence. Maintain the supply and use the control input as shown in the timing diagram.
Typical applications
- Delayed timed energization of a control load
- Pulse generation after an adjustable delay
- Equipment sequencing with a defined output-pulse duration
Specify your enquiry
For a focused quotation, include:
- Control supply version: AC/DC 24-240V or AC 230V
- Initial delay, pulse duration and reset-input requirements
- Load characteristics, quantity and delivery destination
Download NewTrend RT6-P1 datasheet (PDF)
Product reference images and drawings
Terminal connections
Delay t1 and pulse duration t2
Common housing dimensions; RT6-P1 front view shown.
Set the initial delay t1 and the output pulse duration t2 separately. Use the S-A1 input to reset timing as shown in the connection and timing diagrams. Each interval equals its selected range multiplied by its 10%-100% fine adjustment. Installation and wiring must be performed by qualified electricians.