NewTrend · Multifunction timer relay
Product overview
NewTrend RT6-M1 combines ten selectable timing and switching functions in an 18mm DIN-rail housing. Rotary switches select the function and time range, with a 10%-100% potentiometer for fine adjustment. The 1 SPDT output switches one control circuit. Choose the wide-range AC/DC 24-240V supply or the AC 230V version to match the control circuit.
Technical selection summary
| Model | RT6-M1 |
|---|---|
| Output contacts | 1 SPDT |
| A230 power input | AC maximum 6VA / 1.3W |
| Weight | S240: 63g; A230: 62g |
| Function | 10 functions: A-J; see timing diagrams |
| Supply terminals | A1-A2 |
| Control supply options | S240: AC/DC 24-240V; A230: AC 230V; 50-60Hz |
| Supply tolerance | -15% to +10% |
| S240 burden | AC 0.09-3VA / DC 0.05-1.7W |
| Supply indication | Green LED |
| Time setting | Range selector and 10%-100% potentiometer |
| Adjustment range | 0.1s-10days; ON; OFF |
| Marked time ranges | 1s, 10s, 1min, 10min, 1h, 10h, 1day, 10days; ON and OFF positions |
| Time setting deviation | 10% with mechanical adjustment |
| Repeat accuracy | 0.2% of set value |
| Temperature coefficient | 0.05%/degree C at 20 degrees C |
| Contact rating | 10A, AC-1 |
| Switching voltage | 250VAC / 24VDC |
| Minimum DC breaking power | 500mW |
| Output indication | Red LED |
| Mechanical life | 10,000,000 operations |
| Electrical life (AC-1) | 100,000 operations |
| Reset time | Maximum 200ms |
| Operating temperature | -20 to +55 degrees C |
| Storage temperature | -35 to +75 degrees C |
| Mounting | DIN rail to EN/IEC 60715 |
| Protection | IP40 front panel; IP20 terminals |
| Operating position | Any |
| Overvoltage category | III |
| Pollution degree | 2 |
| Maximum conductor size | Solid: 1 x 2.5mm2 or 2 x 1.5mm2; with sleeve: 1 x 2.5mm2 (AWG 12) |
| Terminal tightening torque | 0.4Nm |
| Body dimensions | 90 x 18 x 64mm |
| Referenced standards | EN 61812-1; IEC 60947-5-1 |
Select the required operating sequence against the A-J timing diagrams and specify the supply version. Modes controlled by S require a continuously applied supply and the corresponding trigger connection.
Operation
- Ten selectable functions cover power-on delay, timed interval, repeat cycling, S-controlled timing, latching and a delayed 0.5-second pulse.
- The wiring and timing diagrams define the operating sequence; confirm the required single-shot and S-input behavior when ordering.
Typical applications
- Lighting and heating control
- Motor, pump and fan control circuits
- Equipment sequencing requiring selectable timing or latching operation
Specify your enquiry
For a focused quotation, include:
- Control supply: AC/DC 24-240V or AC 230V
- Required A-J function, timing interval and trigger behavior
- Load characteristics, quantity and delivery destination
Download NewTrend RT6-M1 datasheet (PDF)
Product reference images and drawings
Supply, S-input and output terminal connections
Ten operating function diagrams A-J
RT6-M1 housing dimensions.
Set delay time as the selected range multiplied by the 10%-100% fine adjustment. ON and OFF provide permanent output states. Confirm the required S-input and reset behavior against the selected timing diagram. Installation and wiring must be performed by qualified electricians.