CHINT · NA1-6300X Drawout ACB, 5000/6300 A
Product overview
CHINT NA1 uses an AC main circuit with separately specified auxiliary control power. Select the complete frame, rated current, controller, poles and mounting reference shown for this page.
Technical selection summary
| Published scope | NA1 legacy X versions; 5000, 6300 A |
|---|---|
| Main circuit | AC50/60 Hz; frame-specific AC400/415/690 V ratings |
| Auxiliary supply | AC220/230, AC380/400, DC110 or DC220 only where the exact reference lists it |
| NA1-6300X Icu / Ics | AC400 V: 120/100 kA; AC415/690 V: 85/75 kA |
| 6300X restrictions | Drawout only; 4000/5000 A: 3P or 4P; 6300 A: 3P only |
DC in the control supply does not mean a DC main-circuit ACB. A DC auxiliary supply needs the specified DC power module. XN/XH and unlisted revisions are not inferred from these X-version references.
Typical applications
- CHINT NA1 uses an AC main circuit with separately specified auxiliary control power.
Specify your enquiry
For a focused quotation, include:
- Selected manufacturer model and configuration
- Application and required quantity
- Destination and required technical documents
Original CHINT English technical document (PDF)
Product reference images and drawings