People Electric · AC Contactor
Product overview
Original People Electric RDC5 AC contactors provide remote making and breaking of motor and distribution circuits. This listing covers normal-type three-pole contactors, with source-backed AC-3 ratings from 6 to 95A at 380/400V. An appropriately matched overload relay can be used in a motor-starter assembly. The main-circuit voltage and the control-coil voltage are separate ratings.
Technical selection summary
| Manufacturer / series | Original People Electric RDC5 |
|---|---|
| Published version | Normal type; 3 main poles |
| Selectable rated current | AC-3 at 380/400V: 6A, 9A, 12A, 18A, 25A, 32A, 40A, 50A, 65A, 80A, 95A |
| Main-circuit rated voltage Ue | 380/400V or 660/690V; use the matching duty rating below |
| Rated insulation voltage Ui | 690V |
| Built-in auxiliary contacts | 6–32A: 1NO or 1NC; 40–95A: 1NO+1NC. 38A pending exact configuration. |
| Control-coil voltages | AC 24, 36, 48, 110, 127, 220/230, 240, 380/400, 415 or 440V |
| Coil frequency | 50Hz or 50/60Hz as listed in the manufacturer coil table; confirm the supplied coil |
| Coil operating / release range | Operating: 85–110% Us; release: 20–70% Us |
| Standards stated in catalogue | IEC 60947-4-1; GB 14048.4 |
| Frame-dependent data | Mechanical/electrical life, AC-4 duty, conductor capacity and tightening torque vary by frame. Refer to the complete manufacturer technical table. |
| RDC5-06 AC-3 ratings | At 380/400V: 6A, 2.2kW. At 660/690V: 3.8A, 3kW. |
| RDC5-09 AC-3 ratings | At 380/400V: 9A, 4kW. At 660/690V: 6.6A, 5.5kW. |
| RDC5-12 AC-3 ratings | At 380/400V: 12A, 5.5kW. At 660/690V: 8.9A, 7.5kW. |
| RDC5-18 AC-3 ratings | At 380/400V: 18A, 7.5kW. At 660/690V: 12A, 10kW. |
| RDC5-25 AC-3 ratings | At 380/400V: 25A, 11kW. At 660/690V: 18A, 15kW. |
| RDC5-32 AC-3 ratings | At 380/400V: 32A, 15kW. At 660/690V: 22A, 18.5kW. |
| RDC5-38 AC-3 ratings | At 380/400V: 38A, 18.5kW. At 660/690V: 22A, 18.5kW. |
| RDC5-40 AC-3 ratings | At 380/400V: 40A, 18.5kW. At 660/690V: 34A, 30kW. |
| RDC5-50 AC-3 ratings | At 380/400V: 50A, 22kW. At 660/690V: 39A, 33kW. |
| RDC5-65 AC-3 ratings | At 380/400V: 65A, 30kW. At 660/690V: 42A, 37kW. |
| RDC5-80 AC-3 ratings | At 380/400V: 80A, 37kW. At 660/690V: 49A, 45kW. |
| RDC5-95 AC-3 ratings | At 380/400V: 95A, 45kW. At 660/690V: 49A, 45kW. |
Current buttons refer to AC-3 duty at 380/400V. Do not apply those current or motor-power values at 660/690V or in AC-4 duty. This listing covers normal-type 3P versions only. Reversing, dust-cover, 4P and 2NO+2NC versions are not included. The catalogue lists a 38A frame but leaves its built-in auxiliary-contact coding unclear; 38A therefore remains unavailable here. Series photographs can show other ratings or auxiliary arrangements. Confirm the supplied coil frequency and complete ordering reference with the quotation.
Typical applications
- Remote switching of AC motors within the documented utilization-category ratings.
- Motor starter assemblies with a correctly selected overload relay.
Specify your enquiry
For a focused quotation, include:
- Main-circuit voltage, load type and required AC-3 or AC-4 duty.
- Rated current, built-in auxiliary contacts, AC coil voltage and coil frequency.
- Quantity, overload-relay requirement, destination and project documents.
Download People Electric RDC5 catalogue (PDF)