DELIXI · Electrical fire monitoring
Product overview
CDFLS is the DIN-rail detector in the latest manufacturer sample, used with a CDFL-Z host. The existing panel-type CDFL gallery photograph is a legacy series reference.
Technical selection summary
| Monitoring choices | CDFLS1:1 residual-current +4 temperature channels; CDFLS4:4+4; CDFLS8:8+4, per2026 sample. Exact supplied power/interface remains to be verified before a full variant is selected. |
|---|---|
| Alarm settings | Residual-current alarm200–1000mA,1mA steps; temperature45–140°C,1°C steps. |
| Output contact rating | 1A/AC125V or3A/DC24V. These are output-contact ratings, not the detector supply voltage. |
| Detector outline | 71×88×56mm per the original CDFLS drawing;52/62mm front references retained. |
| Power / communications conflict | The2026 table and outline markAC220V, while its product photograph marksDC24V. It also contains powerbus and485 descriptions. These are not offered as one universal supply/interface. |
| CDFL-Z host, separate device | Up to500 detectors and4000 records per sample; host parameters are not transferred to the detector. |
The requested newer CDFLS scope is recorded. Confirm actual supplied power and bus version; do not wire from the older CDFL photograph or assume AC/DC interchangeability.