DELIXI ELECTRIC · DZ47vG
Product overview
DELIXI DZ47vG provides manually operatedAC isolation. This page follows the exact2026.04.23 switch-disconnector manual, notDZ47GQF over/undervoltage products.
Technical selection summary
| Rated current | 20/25/32/40/63/80/100/125A in the exact manual; no unlisted50A is inferred |
|---|---|
| Pole / voltage | 1P:AC230V; 2P/3P/4P:AC400V |
| Utilization | 20–63A:AC-22A; 80–125A:AC-21B |
| Short-time / insulation | 20–63A:Icw15Ie for 1s, Ui500V; 80–125A:Icw1500A for 1s, Ui690V. Uimp6kV |
| Protection / terminals | No overcurrent trip; coordinate upstream protection.20–63A torque2.5Nm; 80–125A3.5Nm; DINTH35-7.5 mounting |
| Auxiliary / drawings | LeftOF auxiliary is documented for 80–125A only. Original dimensions, terminal markings, conductor table and circuit diagrams retained |
The model hint is a selection description, not an invented material code. Confirm the exact factory reference for any optionalOF contact. This isolator does not provide over/undervoltage or overload protection.
Typical applications
- DELIXI DZ47vG provides manually operatedAC isolation.