Product overview
CHINT NM3DC high-voltage DC moulded-case circuit breakers use separate 400 A and 630 A frame selections. Match the complete HV breaking-capacity, trip-unit, current and pole code.
Technical selection summary
| Frame versus rated current | The referenced HV table lists a 400 A frame with 200–400 A rated-current selections and a 630 A frame with 200–630 A selections. A frame designation is not the actual ordered current. |
|---|---|
| Exact HV family rating | For the referenced 2P HV construction, the table specifies Ue DC 1500 V, Ui 1500 V and Uimp 12 kV. Do not transfer these values to an NM3DC version without the matching HV code and wiring. |
| DC short-circuit reference | The referenced HV table lists Icu 15 kA at the stated DC 1500 V condition. These are not AC ratings or per-pole voltage rules. |
| Trip-unit reference | The referenced construction is thermal-magnetic (TM). Select the exact instantaneous characteristic and rating code; no independently adjustable electronic L/S/I trip unit is implied. |
The original 200–630 A entries span more than one frame. Confirm the complete HV/F/TM ordering code, actual current, polarity/connection diagram and installation conditions before selection. A two-pole DC rating must not be extended to a single pole or another grounding arrangement.
Typical applications
- Control or distribution assemblies matched to the exact model and operating duty.
- Replacement procurement with complete manufacturer-code verification.