CHINT · Air circuit breaker
Product overview
CHINT NXA air circuit breakers are used for main distribution protection with a choice of intelligent controllers and operating accessories. Frame size alone does not define the complete breaker: provide the rated current, breaking-capacity code, poles and control supply with the enquiry.
Technical selection summary
| Series | NXA |
|---|---|
| Frame sizes | 1600, 2000, 3200, 4000 and 6300 A |
| Breaking-capacity codes | N, S and H, depending on model |
| Operating voltage families | 380/400/415 V and 440/525/690 V AC |
| Poles | 3P or 4P |
| Installation | Fixed or drawout |
| Accessories | Operating mechanism, releases, indication and interlocks are configuration-dependent |
| NXA1600N fault-rating reference | Icu / Ics: 50 / 42 kA at AC 380/400/415 V; 30 / 30 kA at AC 440/525/690 V, as listed in the CHINT NXA catalogue |
| NXA3200H fault-rating reference | Icu / Ics: 100 / 85 kA at AC 380/400/415 V; 70 / 70 kA at AC 440/525/690 V |
| NXA6300H fault-rating reference | Icu / Ics: 120 / 120 kA at AC 380/400/415 V; 85 / 85 kA at AC 440/525/690 V. The catalogue specifies 3P for the 6300 A rating |
| Breaking versus withstand ratings | Icu is ultimate breaking capacity and Ics is service breaking capacity. Icw is a separate short-time withstand rating with a stated duration; a 3-second Icw value is not an Icu rating. Confirm the complete frame, N/S/H capacity code, poles and operating voltage |
Typical applications
- Main switchboard incomers
- Industrial power distribution
- Distribution projects requiring selective protection