NewTrend / OEM · Vacuum contactor
Product overview
The NewTrend / OEM CKJ5 family uses vacuum interrupters for remote switching of AC motor circuits. The supplied family table covers several frames; select a frame and control supply to match the operating current, voltage and duty.
Technical selection summary
| Family / main poles | CKJ5 / 3 poles |
|---|---|
| Frame groups in supplied table | 160, 250, 400 and 630 A frames with lower-current variants |
| Listed current range | 80–630 A across different frames |
| Main-circuit voltage reference | Up to 1140 V AC; confirm the selected unit |
| Frequency | 50/60 Hz |
| Control supply reference | AC 220/380 V or DC 110/220 V; confirm exact coil construction |
Frame-specific dimensions and endurance differ. Select from the matching drawing rather than the family maximum. This contactor alone does not establish an explosion-proof assembly or approval for a hazardous location.
Typical applications
- Industrial motor switching
- Remote motor-control assemblies
- OEM starter panels with matched protection
Product reference images and drawings
Compare the exact model, voltage and duty. Reference tables may include other frames or versions; confirm the ordered configuration before using any rating or dimension.
Model comparison
| Model | CKJ5-160/1140 | CKJ5-250/1140 | CKJ5-400/1140 | CKJ5-630/1140 | ||
| Main Circuit | Rated working current (Ie) | 80A, 125A, 160A | 200A, 225A, 250A | 400A | 500A, 630A | |
| Rated working voltage (Ue) | 1140V | |||||
| Rated frequency (fr) | 50/60Hz | |||||
| Rated making capacity (100 times) | 10Ie | |||||
| Rated breaking capacity (25 times) | 8Ie | |||||
| Limit breaking capacity (3 times) | 2000A | 4500A | 4500A | 6000A | ||
| Withstand Voltage (power frequency) | 4200V | |||||
| Control circuit | Rated voltage (Us) | AC. 220/380V, DC. 110/220V, or other Customerized control voltage | ||||
| Withstand Voltage (power frequency) | 2000V | |||||
| Rated power (Ps) electric holding | absorbing | ≤600VA | ||||
| holding | ≤50VA | |||||
| Auxiliary circuit | Form | 2a+1b | 4a+3b | |||
| Withstand Voltage (power frequency) | 2500V | |||||
| Rated value | AC 380V/5A, DC 380V/1A | |||||
| Main Contact Parameter | fixed – moving contact distance | 1.8±0.2mm | 2.0±0.2mm | |||
| Overtravel | 1.0±0.2mm | |||||
| Final pressure | 30±3N | 78±7.8N | 117.6±11.8N | 196±19.6N | ||
| Rated operating frequency | Long-term (AC-3) | 600 times/h | ||||
| Long-term (AC-4) | 300 times/h | |||||
| Short-term | 3000 times/h | 2000 times/h | ||||
| Mechanical endurance | 3,000,000 times | |||||
| Electrical endurance | AC-3 | 600,000 times | ||||
| AC-4 | 60,000 times | 20,000 times | 5,000 times | |||
| Mechanical characteristics | Closing time | ≤200ms | ||||
| Original opening time | ≤160ms | |||||
| 3-phase synchronism | ≤3ms | |||||
| Closing tripping | ≤10ms | |||||