CHINT · Air circuit breaker
Product overview
The CHINT NXA air circuit-breaker family protects low-voltage distribution circuits. This page covers the 1600–6300 A selection scope; match the frame, breaking-capacity code, controller, installation and full rated-current code before ordering.
Technical selection summary
| Manufacturer family | NXA; exact order includes frame, N/S/H version, current code and controller/installation/poles |
|---|---|
| Current choices on this page | 1600A, 2000A, 2500A, 3200A, 3600A, 4000A, 5000A, 6300A |
| Frame mapping | 1600 frame: up to 1600 A; 2000 frame: up to 2000 A; 3200 frame: 1600/2000/2500/3200 A; 4000 frame: 3200/3600/4000 A; 6300 frame: 4000/5000/6300 A |
| Pole restriction | 3P or 4P; 6300 A is only 3P in this reference. The 4P neutral rating for the 6300 frame differs from phase rating |
| Installation | Fixed or draw-out; confirm the complete construction and chassis |
| Main circuit | AC 380/400/415 or 440/525/690 V; 50/60 Hz |
| Breaking and protection | N/S/H breaking codes and M/A/P/H controller codes are separate selections; values differ by frame, voltage and controller |
| Manufacturer standard | IEC/EN 60947-2; apply cabinet-temperature and altitude derating |
Rated current is not a free adjustment across every frame. A 6300 A four-pole configuration is excluded. The H breaking-capacity code is separate from an H harmonic controller. Supply voltage, auxiliary control voltage, neutral protection and the complete order code must be verified together.
Typical applications
- Main incoming and distribution switchgear
- Coordinated low-voltage protection systems
Product reference images and drawings
Match the exact model, construction and supplied revision. Family reference pages can show other ratings or versions.