NewTrend / OEM · Miniature contactor
Product overview
This NewTrend / OEM LP1K listing covers 6 A, 9 A or 12 A motor-duty frames with 24 V DC coil. Specify the full contact code, control-coil supply and connection style so the selected unit fits the circuit and panel layout.
Technical selection summary
| Series / listing | LP1K |
|---|---|
| Configuration | 6 A, 9 A or 12 A motor-duty frames with 24 V DC coil |
| Coil family | LC1K / LC2K: AC coil; LP1K: DC coil; full suffix required |
| Contact arrangement | 3 main poles; confirm NO/NC auxiliary arrangement |
| Connection / mounting | Select terminal and mounting version from the exact drawing |
AC/DC in this family refers to the coil version. Confirm the main-circuit load and utilization category separately. A three-pole motor-duty rating must not be assumed for a four-pole mixed NO/NC contact arrangement. Reference drawings represent specific constructions, not every suffix. Confirm screw-clamp, Faston, spring-terminal or PCB-pin construction and its matching outline. Auxiliary blocks, LR2K overload relays, reversing interlocks and star-delta assemblies require a documented compatible combination; motor-power data must match voltage and utilization category.
Typical applications
- Compact control panels
- OEM switching assemblies
- Motor control with a matched overload relay
Product reference images and drawings
Use the matching model and version in the reference data. Confirm the applicable rating, test conditions and dimensions against the exact supplied unit.
Model comparison
| Model Number | LC1K06 | LC1K09 | LC1K12 | LC1K16 | LP1K06 | LP1K09 | LP1K12 | LP1K16 |
| Rated operational current (AC-3, 380V) | 6A | 9A | 12A | 16A | 6A | 9A | 12A | 16A |
| Rated operational current (AC-3, 660V) | 5A | 7.5A | 10A | 12A | 5A | 7.5A | 10A | 12A |
| Coil voltage (Control circuit voltage) | AC 230V 240V 380V 415V | DC 220V 230V 240V 250V | ||||||
| Rated operational voltage | 380V, 660V | |||||||
| Rated insulation voltage | 690V | |||||||
| Main and auxiliary contacts | 3P+NO, 3P+NC, 2NO+2NC | |||||||
| Motor power (AC-3, 220/240V) | 1.5KW | 2.2KW | 3KW | 3KW | 1.5KW | 2.2KW | 3KW | 3KW |
| Motor power (AC-3, 380/415V) | 2.2KW | 4KW | 5.5KW | 7.5KW | 2.2KW | 4KW | 5.5KW | 7.5KW |
| Motor power (AC-3, 440V) | 3KW | 4KW | 5.5KW | 7.5KW | 3KW | 4KW | 5.5KW | 7.5KW |
| Motor power (AC-3, 500/660/690V) | 3KW | 4KW | 4KW | 4KW | 3KW | 4KW | 4KW | 4KW |
| Mouting type | DIN Rail / PCB Solder Pin / Plate | |||||||
| Coil Pull-In Voltage | 0.85-1.1 Us | |||||||
| Coil Drop-Out Voltage | 0.2-0.75 Us | ≤0.2 Us | ||||||
| Coil power | Pull-In 40VA, Maintain 4VA | |||||||
| Coil power consumption | 1.2W | |||||||
| Coil Pull-In time | 6-18 ms | |||||||
| Coil Drop-Out time | 5-12 ms | |||||||
| Electrical life | 500 thousand times | |||||||
| Mechanical life | 100 thousand times | |||||||
| Ambient air temperature | -5…40 °C | |||||||
| Operating altitude | 2000 m without derating in temperature | |||||||
Control coil voltage codes
| LC1K (AC voltage coil) | |||||||||||||||||
| Volts (50/60Hz) | 12 | 20 | 24 | 36 | 42 | 48 | 110 | 115 | 120 | 127 | 200/ 208 | 220/ 230 | 230 | 230/ 240 | 256 | 277 | 380/ 400 |
| Code | J7 | Z7 | B7 | C7 | D7 | E7 | F7 | FE7 | G7 | FC7 | L7 | M7 | P7 | U7 | W7 | UE7 | Q7 |
| Volts (50/60Hz) | 400 | 400/ 415 | 440 | 480 | 500 | 575 | 600 | 660/ 690 | |||||||||
| Code | V7 | N7 | R7 | T7 | S7 | SC7 | X7 | Y7 | |||||||||
| LP1K (DC voltage coil) | |||||||||||||||||
| Volts | 12 | 20 | 24 | 36 | 48 | 60 | 72 | 100 | 110 | 125 | 155 | 174 | 200 | 220 | 230 | 240 | 250 |
| Code | JD | ZD | BD | CD | ED | ND | SD | KD | FD | GD | PD | QD | LD | MD | MPD | MUD | UD |
Complete model number explained
| LP1K09105BD: | |
| LP1K means DC coil contactor, LC1K means AC coil contactor | |
| 09 means AC-3 9A rated current | |
| 10 means NO auxiliary contact, 01 means NC auxiliary contact | |
| 5 means PCB Solder Pin type, without 5 means regular DIN Rail type | |
| BD means the coil voltage code |