NewTrend / OEM · Automatic transfer switch
Product overview
The W2R overview describes DIN-rail automatic and manual transfer between normal and standby AC supplies. Specify the complete current, pole and controller configuration.
Technical selection summary
| Listing / reference model | W2R series |
|---|---|
| Product type | Automatic transfer switch |
Confirm source voltages, neutral switching, transfer timing, interlock and protection coordination for the exact variant. A transfer switch does not by itself establish uninterrupted power or a fault-clearing function. Confirm source sensing, transfer sequence, interlock, pole/neutral arrangement, manual operation and controller options. Transfer time is not a guarantee of uninterrupted power; fault withstand and service life require the tested assembly and protective-device combination.
Product reference images and drawings
Use the matching model and version in the reference data. Confirm the applicable rating, test conditions and dimensions against the exact supplied unit.
| Model | W2R | ||
| Rated Current le: A | 63A, 100A, 125A | ||
| Insulation Voltage Ui | AC690V 50/60Hz | ||
| Rated Voltage Ue | AC400V 50/60Hz | ||
| Grade | PC Class; None over load and short circuit protection | ||
| Pole | 2P | 3P | 4P |
| Weight(Kg) | 0.65 | 0.75 | 0.85 |
| Electrial Life | 2000times | ||
| Mechanical Life | 5000times | ||
| Reted Conditional Short Circuit Current Iq | 50KA | ||
| SCPD(Fuse) | RT16-00-63A | ||
| Reted Impilse withstand voltage | 8KV | ||
| Control Circuit Us | AC220V 50/60Hz | ||
| Working Voltage Range | 85%-110%Us | ||
| Auxiliary Circuit | 2Independent Relays with 2 transfer contact. Contact Capacity: AC220V 50/60Hz, le=5A | ||
| Contact Transfer Time | 30ms | ||
| Operation Transfer Time | 30ms | ||
| Return Transfer Time | 30ms | ||
| Off-Time | 30ms | ||