NewTrend / OEM · DIN-rail automatic transfer switch
Product overview
The NLQ4 listing concerns a special PV-system-to-mains transfer application. Confirm the inverter output, mains arrangement and controller logic for the exact supplied unit.
Technical selection summary
| Listing / reference model | NLQ4 PV-to-mains reference |
|---|---|
| Product type | DIN-rail automatic transfer switch |
| Application boundary | PV-system-to-city-power special-use reference; no implied DC switching or source paralleling |
| System selection | Confirm AC operating voltage/frequency, poles, neutral arrangement and current for the exact code |
| Installation | DIN-rail mounting; verify enclosure and connection dimensions |
| Transfer duty | Confirm source sensing, interlock, switching/action time and load interruption |
Keep the stated special-use limitation and match the controller logic to the inverter and mains arrangement. A PV application reference does not establish DC switching capability or permission to parallel supplies. Confirm exact AC/DC circuit duties, poles, interlock and current against the offered unit before ordering. The AC reference entries below require confirmation for the exact version. The 60A prose and 16–100A list conflict; no current, fault or timing entry is a guaranteed supplied-unit rating.
Product reference images and drawings
Use the matching model and version in the reference data. Confirm the applicable rating, test conditions and dimensions against the exact supplied unit.
Model-specific AC reference data
| Current entries | 16A, 20A, 25A, 32A, 40A, 50A, 63A, 100A; separate prose states 60A |
|---|---|
| Insulation reference | AC690, 50HZ |
| Operating reference | AC400, 50HZ |
| Impulse withstand reference | 8KV |
| Poles and weight references | 2P / 1.7 KG; 3P / 2.1 KG; 4P / 2.6 KG |
| Making/breaking test reference | 6.0Ie, 1.05Ue, cosØ=0.50±0.05, 50 times |
| Operating test reference | 2.0Ie, 1.05Ue, cosØ=0.80±0.05, 6000 times |
| Conditional short-circuit reference | Iq 50KA; SCPD RT16-00-63A fuses; exact tested combination required |
| Control supply reference | Us AC220V, 50HZ; 85% Us–110% Us |
| Ancillary contact reference | Two isolated relays, each with 2 groups of passive contacts; AC220 50Hz, Ie=5A |
| Timing references | Switching time <50ms; action time <50ms; interruption and controller conditions require confirmation |