People Electric · Photovoltaic DC Fuse
Product overview
People Electric RDT8-PV fuse links provide gPV DC overcurrent protection for photovoltaic generation and energy-storage circuits. The matching holder carries the fuse link and provides the specified isolation function. Select a holder or fuse link explicitly: holder current ratings and fuse-link current ratings are different.
Technical selection summary
| Manufacturer / series | Original People Electric RDT8-PV |
|---|---|
| 1000V version | RDT8-32PV holder: DC1000V, 32A; matching fuse link: 10×38mm |
| 1500V version | RDT8-63PV holder: DC1500V, 63A; matching fuse link: 10×85mm |
| Documented fuse-link current choices | 2, 3, 4, 5, 6, 8, 10, 12, 15, 20, 25 and 30A for both sizes |
| Fuse utilization | gPV, full-range DC breaking capability |
| Holder utilization / protection | DC-PV0; IP2X, as stated in the source table |
| Fuse breaking capacity | 20kA |
| Holder peak withstand current | 20kA |
| Minimum fusing current | 1.45 × In |
| Mounting | TH35-7.5 rail; vertical installation |
| Altitude current correction | ≤2,000m: 1.0; above 2,000 to 3,000m: 0.9; ≥3,000m: 0.8, as tabulated |
| Standards stated | GB/T 14048.3; GB/T 13539.1; GB/T 13539.6 |
Choose the component and current separately. A 32A or 63A holder does not mean a fuse link of the same current is included. Only the documented 2–30A fuse-link steps are offered here. The 10×38mm/DC1000V and 10×85mm/DC1500V versions are not interchangeable. Confirm fuse/holder quantities and protection coordination before ordering.
Typical applications
- DC-side overcurrent protection in photovoltaic power-generation systems.
- Coordinated DC overcurrent protection in energy-storage installations within the selected fuse voltage and current ratings.
Specify your enquiry
For a focused quotation, include:
- Holder or fuse link, exact version, current rating and quantity of each component.
- Actual maximum DC voltage, prospective fault current, circuit design, ambient conditions and installation altitude.