Product overview
Structure families
The manufacturer identifies five structural types: A external bypass starter, B bypass cabinet, C online starter, D online cabinet and E built-in bypass starter.
SCR and microprocessor control
The SCR drive supports controlled motor acceleration and deceleration. LCD parameter setup covers start voltage, ramp times, current limits and related protections. Refer to the factory settings and parameter tables below.
Model and configuration selection
A–E are structure codes. The example 55A-T4M explains the code format. A complete model includes the manufacturer’s product prefix, which is not supplied for every configuration. Confirm the complete order code.
Original technical diagrams


Model nomenclature
| Code Segment | Designation | Specification Details |
|---|---|---|
| □□□ | Product Code | Enterprise/series model identifier |
| 55 | Power Rating | Applicable motor rated power (e.g., 55kW) |
| A / B / C / D / E | Structural Configuration | A: Bypass soft starter | B: Bypass soft start cabinet | C: Online soft starter | D: Online soft start cabinet | E: Built-in bypass soft starter |
| T4 / T6 | Power Phase & Voltage | T: Three-phase power supply | 4: 380V | 6: 660V |
| M | Communication Function | Indicates RS485 / serial communication capability |
Technical specifications
| Project (Item) | Specification |
|---|---|
| Standards Compliant | GB14048.6 / IEC60947-2-2: 2002 |
| Three-Phase Power | Voltage (AC) 380V ± 15% (220V and 660V Optional) |
| Frequency | 50 / 60Hz |
| Applicable Motor | Squirrel-cage three-phase asynchronous motor |
| Start Frequency | Full-load motor start: no more than 4 times/hour; no-load or light-load: recommended no more than 10 times/hour |
| Degree of Protection | IP20 |
| Shock Resistance (Impact) | Conforms to IEC68-2-27: 15g, 11ms |
| Seismic / Vibration Capacity | Altitude below 3000 meters above sea level, vibration intensity below 0.5g |
| Ambient Temperature | Operating temperature 0~40°C without derating (between +40°C~60°C, derate current by 2% for every 1°C increase) and less than 60°C |
| Storage Temperature | -25°C ~ 70°C |
| Environment Humidity | 93% without condensation or dripping, in compliance with IEC68-2-3 |
| Maximum Operating Altitude | Within 1000 meters altitude without derating (above 1000 meters, derate current by 5% for each additional 100 meters) |
| Cooling Method | Natural air cooling |
| Mounting Orientation (Relative to Vertical) | Vertical installation, tilt angle within ±10° |
Adjustment ranges and factory defaults
| Code | Name | Predetermined Area (Setting Range) | Factory Default | Description |
|---|---|---|---|---|
| F0 | Starting voltage | 30-80% | 30% | Effective in voltage ramp mode; in current limit mode, the starting voltage is fixed at 40% |
| F1 | Soft start time | 2-60S | 16S | Invalid in current limit mode |
| F2 | Soft stop time | 0-60S | 0S | Set to 0 for free stop (coast-to-stop); please set to 0 for one-to-two (dual-motor) drive wiring |
| F3 | Interval delay | 0-999S | 0S | Sets the interval time between starts to prevent equipment damage from frequent starting |
| F4 | Programming delay | 0-999S | 0S | Used for programmable relay output delay |
| F5 | Starting limit current | 50-500% | 280% | Effective in current limit mode; in voltage ramp mode, the maximum current limit is 400% |
| F6 | Maximum operating current | 50-200% | 100% | Percentage of the rated current of the motor |
| F7 | Under-voltage protection | 40-90% | 80% | Protection trips when supply voltage falls below the set value |
| F8 | Overvoltage protection | 100-140% | 120% | Protection trips when supply voltage exceeds the set value |
| F9 | Start mode | 0-5 | 1 | 0: Current limit | 1: Voltage ramp | 2: Kickstart + Current limit | 3: Kickstart + Voltage ramp | 4: Current ramp (slope) | 5: Dual closed-loop |
| FA | Output protection allowed | 0-4 | 4 | 0: Primary | 1: Light load | 2: Standard | 3: Heavy load | 4: Advanced |
| FB | Operation control method | 0-6 | 1 | 0: Keypad | 1: Keypad + External control | 2: External control | 3: External control + Communication | 4: Keypad + External control + Communication | 5: Keypad + Communication | 6: Communication | 7: Start/stop prohibited |
| FC | Parameter modification allowed | 0-2 | 1 | Please refer to the manual for details |
| FD | Communication address | 0-63 | 0 | Used for multi-unit communication between multiple soft starters and a host computer |
| FE | Programming output | 0-19 | 7 | Run relay output (terminals 03, 04) setting |
| FF | Soft stop current limit | 20-100% | 80% | Please refer to the manual for details |
| FP | Motor rated current | — | Rated value | Used to input the nominal rated current of the motor |
| FU | Bypass delay | 1-99S | 5 | Increases the bypass switching delay time |
| FL | Three-phase balance allowed | 0-1 | 1 | 0: Prohibited | 1: Permitted |
| FM | Current coefficient | 50-150% | 100% | Decrease coefficient if displayed current is higher than actual; increase if lower |
| FN | Voltage coefficient | 50-150% | 100% | Decrease coefficient if displayed voltage is higher than actual; increase if lower |
Typical applications
Three-phase squirrel-cage motors in fans, pumps, conveyors, compressors and industrial equipment.