Product overview
SCR starting control
The microprocessor controls SCR conduction during starting and stopping. Torque and current control reduce the starting shock on the supply and driven equipment.
External bypass
An external contactor carries continuous motor current after acceleration. Configurable bypass delay, LCD parameter setting and RS485 support integration and monitoring. The source describes overload, phase loss, current imbalance, stall, voltage and thermal protections.
Model and configuration selection
Motor power options use the published frame ranges. Confirm the exact order code, full-load current, main supply and external bypass contactor for the selected motor.
Original technical diagrams
Circuit and terminal functions
| Circuit Block | Terminal Marking | Engineering Function & Operating Description |
|---|---|---|
| Primary Power Circuit | L1, L2, L3 → R, S, T | Three-phase main AC power input (380V/400V/415V/690V, 50/60Hz) routed through an external Moulded Case Circuit Breaker (MCCB) or residual current breaker to soft starter input terminals R, S, T. |
| U, V, W & KM Contactor | Soft starter output terminals U, V, W connect directly to three-phase induction motor (M). External AC bypass contactor (KM) connects in parallel between R-S-T and U-V-W to handle running current after full-voltage startup. | |
| Secondary Relay Outputs | 01, 02 (K3 Output) | Full Pressure Output Relay (Ue=100%): Closes automatically when the motor ramp completes and full terminal voltage is reached, energizing the KM bypass contactor coil. |
| 03, 04 (K2 Output) | Programmable Delayed Output Relay: Configurable delayed auxiliary switching for process sequencing, lubrication pump interlock, or damper control. | |
| 05, 06 (K1 Output) | Fault Alarm Output Relay: Normally open/closed contact trips instantly upon any of the 12 fault states, interlocking the main circuit breaker and signaling DCS/PLC alarms. | |
| Control Inputs & Analog Output | 07 & 10 (Instant Stop) | Emergency coast-to-stop input (NC contact). Instantly cuts all thyristor gates and de-energizes bypass contactor. |
| 08 & 10 (Stop) | Controlled soft stop push-button input (NC contact). Triggers programmable soft deceleration voltage ramp. | |
| 09 & 10 (Start) | Soft start push-button input (NO contact). Initiates soft start cycle according to selected ramp mode. | |
| 11, 12 (Analog Output) | Standard isolated DC 4–20mA analog current loop output proportional to 0–100% motor load current, enabling direct transmission to external ammeters, chart recorders, or PLC analog input cards. |
Outline and mounting dimensions
| Specification | Overall dimensions (mm) | Installation size (mm) | Weight (kg) | ||||
|---|---|---|---|---|---|---|---|
| W1 | H1 | D | W2 | H2 | d | ||
| 5.5-75KW | 145 | 270 | 160 | 132 | 250 | M6 | ≤3.5 |
| 75-220KW | 260 | 520 | 200 | 195 | 375 | M8 | ≤20 |
| 250-350KW | 290 | 560 | 250 | 260 | 460 | M8 | ≤25 |
| 400-450KW | 330 | 590 | 250 | 265 | 500 | M8 | ≤30 |
| 500-630KW | 410 | 670 | 250 | 345 | 550 | M8 | ≤40 |
Typical applications
Fans, pumps, conveyors, compressors and industrial drive systems.