Product overview
Online SCR control
Three-phase input feeds a three-phase motor through a full-time online SCR power stage. The unit ramps motor acceleration and remains in circuit during running.
Cooling, protection and integration
The source describes forced-air cooling, phase loss and unbalance detection, overload and thermal protection. The interface supports relay outputs, 4–20 mA monitoring and RS485 as detailed in the terminal table.
Model and configuration selection
Motor power options use the published frame ranges. Confirm the exact order code and verify motor current, duty and cooling requirements for the selected build.
Original technical diagrams


Motor protection functions
| No. | Protection / Function Item | Trigger Condition & Operating Threshold | Action / Trip Time |
|---|---|---|---|
| 1 | Phase Loss (Open-Phase) Protection | Any single phase of the three-phase power supply has an open circuit / phase failure | < 1 min |
| 2 | Three-Phase Unbalance Protection | Three-phase current unbalance ratio K1 > 10% | < 10 min |
| 3 | Over-Current (Locked-Rotor) Protection | Motor rotor stalls or locks during operation | Delay (±1) s trip |
| 4 | Over-Voltage Protection | Power supply voltage exceeds Ue > 120% | < 1 s |
| 5 | Under-Voltage Protection | Power supply voltage drops to (60%–75%) Ue | < 60 s |
| 6 | Reset Function | Fault clearance and system recovery operation | Manual Stop Key Reset |
| 7 | Over-Temperature Protection | Soft starter internal heatsink temperature exceeds safe operating limit | Auto Shut-Off & Overheat Fault Alarm |
Terminal and control functions
| Terminal / Circuit Group | Terminal Designation | Wiring Function & Technical Description |
|---|---|---|
| Main Power Circuit | R, S, T → U, V, W | Three-phase 380VAC 50/60Hz main power input (L1, L2, L3 via Circuit Breaker / Earth Leakage Circuit Breaker to R, S, T) and direct output (U, V, W) to three-phase motor (M). |
| Control Power Supply | A1, A2 (with Fuse FU) | Secondary control power input protected by fuse FU (connected to N or L3 and phase line as indicated on schematic). |
| Relay Outputs (K1, K2, K3) | 01–02 / 03–04 / 05–06 | 01, 02 (K3): Run output (closes when Ue = 100% full-voltage operation is reached) 03, 04 (K2): Delayed output (programmable relay output) 05, 06 (K1): Fault output (trips upon protection alarm) |
| External Control Inputs | 07, 08, 09, 10 (+DC12V) | Internal +DC12V control loop: 07: Instant Stop (Emergency/Coast Stop) | 08: Stop | 09: Startup (Run) | 10: Common Terminal (Public Side). |
| Analog & Serial Port | 11, 12 & RS485 Port | 11 (+), 12 (−): Analog output DC 4–20mA for remote current monitoring | RS485 Interface: Serial communication port for PLC/SCADA telemetry. |
Outline and installation dimensions
| Specification | Overall dimensions (mm) | Installation size (mm) | Weight (kg) | ||||
|---|---|---|---|---|---|---|---|
| W1 | H1 | D | W2 | H2 | D | ||
| 5.5-45kW | 148 | 310 | 200 | 85 | 275 | M6 | <5 |
| 55-90kW | 210 | 370 | 260 | 150 | 320 | M8 | <12 |
| 115-220kW | 380 | 500 | 240 | 320 | 440 | M8 | <25 |
| 250-400kW | 430 | 600 | 265 | 370 | 520 | M8 | <30 |
| 450-630kW | 620 | 780 | 325 | 570 | 660 | M8 | <50 |
Typical applications
Ventilation equipment, pumps, air compressors, crushers and other industrial motors.