Product overview
Reduced-voltage starting
A three-phase autotransformer limits starting current on squirrel-cage induction motors during infrequent starts. The 65% and 80% taps provide different voltage and starting-torque levels.
Duty and protection
The manufacturer limits starting current to four times motor rated current and cumulative start duration to 30 seconds. Observe the documented cooling and environmental requirements. The starter provides overload, under-voltage and phase-loss protection.
Model and configuration selection
The published family range starts at 10 kW. Model buttons use the explicit power examples in the source nomenclature and the YFX01 prefix. Confirm voltage pairing and any additional ratings before ordering.

Model designation
| Symbol Segment | Designation | Technical Meaning & Explanation |
|---|---|---|
| YF | Enterprise Code | China · Yongfan Electric Co., Ltd. manufacturer identifier |
| X | Voltage Reducing Starting Box | Step-down reduced voltage starter enclosed box type |
| 01 | Autotransformer Series | Design number 01 indicating autotransformer starting scheme |
| □□ | Rated Power | Rated capacity of controlled electric motor in kilowatts (kW) (e.g., 14, 20, 28, 40, 55, 75, 80, 100, 115, 135, 160, 180, 200, 225, 260, 280, 300, 320kW) |
Starting duty and protective functions
| Performance Parameter | Specified Limit / Value | Operational Requirement & Engineering Rationale |
|---|---|---|
| Maximum Starting Current | ≤ 4 × Ie | Controlled via autotransformer step-down taps to minimize grid shock during motor acceleration |
| Max Starting Time (Single / Cumulative) | ≤ 30 s | Maximum permissible energized duration for autotransformer windings during starting transition |
| Mandatory Cooling Duration | ≥ 2 Hours | Required after cumulative 30s starting time to prevent internal coil thermal relay overload trip |
| Permissible Duty Cycle | Long-Time Intermittent | Designed strictly for infrequent motor starting; not suitable for continuous cycling or high-frequency starts |
| Integrated Motor Protections | Tri-Protection System | Full coverage against motor thermal overload, electrical under-voltage, and phase loss / open phase faults |
Autotransformer taps
| Autotransformer Tap | Voltage Ratio (% Ue) | Starting Torque (% Tst) | Factory Setting & Application Note |
|---|---|---|---|
| Standard Tap (Default) | 65% | Approx. 42.25% | Factory Default Connection: Suitable for standard industrial loads such as centrifugal pumps, fans, and unloaders with minimal inrush impact. |
| High Torque Tap | 80% | Approx. 64.00% | Optional Connection: Easily reconnected on-site if user application requires higher starting torque (e.g. crushers, loaded conveyors, heavy mills). |
Environmental and installation limits
| Item | Environmental / Operating Parameter | Specified Operating Limits | Engineering Notes & Precautions |
|---|---|---|---|
| (1) | Altitude Limit | ≤ 2000 m | Derating required if installed above 2000m |
| (2) | Ambient Air Temperature | -5°C to +40°C (24h Average ≤ +35°C) | Minimum ambient temperature floor is -5°C |
| (3) | Atmospheric Relative Humidity | ≤ 50% at +40°C Wettest month: mean min temp ≤ +20°C, mean max RH ≤ 90% | Higher RH allowable at lower temperatures; anti-condensation measures required if temperature fluctuates |
| (4) | Pollution Degree | Grade 3 | Standard industrial harsh electrical environment |
| (5a) | Installation Inclination | ≤ 5° from vertical/horizontal plane | Ensures proper vertical orientation of magnetic contactors |
| (5b) | Installation Category | Category II & Category III | Compatible with primary sub-distribution and branch circuits |
| (6) | Mechanical Vibration & Impact | Place without noticeable vibration or impact | Avoid direct mounting on intensely vibrating machinery frames |
| (7) | Surrounding Atmospheric Media | Non-explosive medium; free of corrosive gases & conductive dust | Must not contain gases/dust that corrode metals or impair insulation |
Electrical ratings and applicable standards
| Specification Parameter | Rated Engineering Value | Standard & Compliance Notes |
|---|---|---|
| Product Series Model | YFX01 Series | Autotransformer reduced voltage starting box |
| Manufacturing Standard | GB14048.4-2003 / JB/T8752-1998 | National & machinery industry electrical standards |
| Rated Operational Frequency | AC 50 Hz | Three-phase power grid |
| Rated Operational Voltage | Up to 660V and below (380V / 660V) | Three-phase 380V standard / 660V compatible |
| Controlled Motor Capacity Range | 10 kW – 320 kW | Three-phase squirrel-cage induction motors |
| Autotransformer Voltage Taps | 65% (Factory Default) and 80% | Dual tap selection for torque/inrush matching |
| Maximum Starting Inrush Current | ≤ 4 × Ie | Peak line current during start sequence |
| Starting Duration Limitation | ≤ 30 seconds | Single start or cumulative continuous starts |
| Cooling Requirement After 30s Start | ≥ 2 Hours | Guarantees thermal safety of autotransformer core & coil |
| Operating Duty Mode | Long-Time Intermittent Starting | Strictly designed for infrequent motor startup |
| Control Mode Configuration | ≤ 75kW: Auto Control ≥ 80kW: Manual & Auto Dual Control | Selected via transfer switch with adjustable time relay |
| Protective Functions | Overload, Under-Voltage, Phase Loss | Comprehensive protection for motor and supply grid |
Typical applications
Pumps, fans, conveyors, compressors and other three-phase squirrel-cage motor loads.