CHINT · Type 2 AC Surge Protective Device
Product overview
CHINT 252463 NXU-IIG 65kA/275V 3P+N is a four-module Type 2 surge protective device for AC distribution systems. Its plug-in protective modules limit transient overvoltage and discharge surge energy through the L-N and N-PE protection paths. This ordering code is the version without a remote monitoring port.
Technical selection summary
| Ordering code | 252463 |
|---|---|
| Manufacturer model | NXU-IIG 65kA/275V 3P+N |
| Product type | AC surge protective device (SPD) |
| SPD test class | Type 2 / Class II |
| Poles | 3P+N |
| Maximum continuous operating voltage (Uc) | 275 V AC (L-N); 255 V AC (N-PE) |
| Frequency | 50/60 Hz |
| Maximum discharge current (Imax, 8/20 μs) | 65 kA |
| Nominal discharge current (In, 8/20 μs) | 30 kA |
| Voltage protection level (Up) | 1.6 kV (L-N); 1.5 kV (N-PE) |
| Remote monitoring port | Without remote monitoring port |
| DIN width | 4 modules / 72 mm |
| Ingress protection | IP20 |
| Dimensions (H × W × D) | 81.9 × 72 × 65.7 mm |
| Reference standard | IEC/EN 61643-11 |
| Construction | Plug-in protective modules and base |
| Status indication | Green: normal protection; red: replacement required |
| Units per pack / carton | 3 / 45 |
| EAN | 6941498992887 |
Imax and In are surge discharge currents, not continuous load currents. Select Uc and the protection arrangement to suit the supply and earthing system. The official product-page photograph is a series representative image showing a 440 V /F version; the specifications for code 252463 are the 275 V version without a remote monitoring port listed above.
Product features
- Type 2 protection for transient overvoltage in AC distribution circuits.
- 3P+N protection arrangement with L-N and N-PE paths.
- Plug-in protective modules and a DIN-rail base for compact installation.
- Thermal ageing protection and visible green/red status indication.
- Four-module width; this code is supplied without a remote monitoring port.
Typical applications
- Three-phase AC distribution boards.
- Building electrical distribution and control circuits.
- Equipment protection against transient overvoltage in compatible TT and TN-S installations.
Selection notes
Match the maximum continuous operating voltage Uc, surge-discharge rating and protection arrangement to the installation. The 65 kA Imax and 30 kA In values use the 8/20 μs test waveform. This Type 2 product is for transient surge protection; select the upstream protective device and earthing arrangement for the actual circuit.
Product reference images and drawings