Delixi Electric CDB6i Miniature Circuit Breaker






Delixi Electric CDB6i Miniature Circuit Breaker
|
Product Name
|
CDB6i Miniature Circuit breaker
|
|
Brand
|
DELIXI ELECTRIC
|
|
Pole Number
|
1P, 1P+N, 2P, 3P, 3P+N, 4P
|
|
Rated current
|
1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
|
|
Volatge
|
1P 230/400V AC
1P+N 230V AC
2P, 3P, 3P+N, 4P 400V AC
|
|
Breaking Capacity
|
6kA
|
|
Trip curve
|
B, C, D
|
|
Operating temperature
|
-35℃~70℃
|






| Weight | 2 kg |
|---|---|
| Dimensions | 25 × 25 × 25 cm |
| Rated Current |
1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63A |
| Poles |
1P+N |
Download official engineering datasheets, certified test standards (IEC / UL / CE), wiring diagrams, and dimensional drawings for DELIXI CDB6i 1P/1P+N AC MCB Circuit Breaker C10/C16/C20.
Pure engineering specifications, tripping curve parameters, and electrical selection guidance for panel builders and system designers.
Curve B trips at 3–5 In (designed for resistive loads, electric heating, and domestic appliances with negligible inrush). Curve C trips at 5–10 In (the standard international choice for residential and commercial lighting, socket outlets, and small induction motors). Curve D trips at 10–14 In (specifically engineered for high-inrush inductive equipment such as industrial transformers, heavy motors, compressors, and welding circuits).
Breaking capacity (Icn/Icu) must exceed the calculated prospective short-circuit fault current at the installation point. 6kA (IEC 60898-1) is standard for residential consumer units and sub-distribution branch circuits located downstream. 10kA (IEC 60947-2) is required for industrial facilities, main switchboards, commercial distribution panels, or circuits situated close to supply transformers where fault levels are high.
For single-phase 230V circuits: 1P provides active phase protection; 1P+N or 2P isolates both live and neutral lines simultaneously (essential for TT earthing systems and sensitive sub-panels). For three-phase 400V systems: 3P protects balanced 3-wire motor loads; 3P+N or 4P is required for 4-wire mixed single-phase loads to ensure complete neutral disconnection during isolation.
Standard AC breakers cannot safely extinguish DC arcs due to the absence of natural zero-crossing current. For DC circuits (60V to 1000V DC), select specialized DC breakers (such as DZ158-125 DC or NM8NDC series) equipped with permanent magnetic arc-blowout chutes and strictly observe polarity wiring to prevent arc re-ignition.
Standard modular clip-on accessories can be mounted directly on the side without tools: OF (Auxiliary Contact for remote status indication), SD (Alarm Contact for trip fault signaling), MX (Shunt Trip for remote emergency tripping), MN (Under-voltage Release for voltage loss protection), and NXBZ mechanical interlock kits for manual generator/mains transfer switches.