People Electric · Residual Current Circuit Breaker
Product overview
People Electric RDX16LE-63 is an electronic residual-current operated circuit breaker for single-phase or three-phase distribution. The device monitors residual current and disconnects the circuit at its specified sensitivity. Select the correct current and pole/voltage configuration, with suitable upstream overcurrent protection.
Technical selection summary
| Manufacturer / series | Original People Electric RDX16LE-63 |
|---|---|
| Mechanism | Electronic type, identified by E in the original model diagram |
| Poles / main voltage | 2P / AC230V; 4P / AC400V; 50Hz |
| Rated current | 25, 40, 63A |
| Residual operating / non-operating current | 30mA / 15mA |
| Maximum residual breaking time | 0.1s as tabulated |
| Making / breaking ratings | Im and IΔm: 500A for 25A/40A; 630A at In=63A according to the original footnote |
| Conditional short-circuit marking | The pictured 63A/4P example is marked Inc=IΔc=6000A. Confirm the exact ordered rating and upstream SCPD; do not treat this as independent overcurrent protection. |
| Overcurrent protection | Specify coordinated upstream overload/short-circuit protection. No thermal-magnetic curve is offered for this RCCB. |
| Residual waveform type | Not explicitly identified in this source; confirm the exact required waveform type before final order |
| Dimensions | 2P width 36mm; 4P width 72mm; overall height 88mm; maximum depth 78mm. Refer to the original mounting drawing. |
| Mounting / environment | TH35-7.5 rail; -5 to +40°C, average ≤35°C; altitude ≤2,000m; pollution degree 2 |
| Standards marked on original product | IEC 61008-1; GB/T 16916.1 |
The original table offers 25A, 40A and 63A at 30mA only; additional currents or sensitivities are not added. Making/breaking ratings depend on current, as shown in the footnote. Confirm the exact residual waveform response, conditional short-circuit rating, SCPD and installation requirements before ordering.
Typical applications
- Residual-current protection in appropriately coordinated AC230V/AC400V distribution.
- Replacement electronic RCCBs requiring exact pole, voltage, current and sensitivity matching.
Specify your enquiry
For a focused quotation, include:
- 25/40/63A, 2P/AC230V or 4P/AC400V, 50Hz and 30mA.
- Required residual waveform response and exact conditional fault-duty/SCPD coordination.
- Mounting dimensions, installation environment, quantity and destination.
Download People Electric RDX16LE-63 catalogue (PDF)