Nader · NDB5
Product overview
Original Nader NDB5 hydraulic-magnetic circuit breakers. Select an exact electrical version first; supported current, curve and voltage remain linked.
Technical selection summary
| Parameter | Specification |
|---|---|
| Supply identity | Original Nader,confirmed by supplier; old Chint field corrected |
| Single-pole range | 1P AC230/250V orDC80V:0.5-63A in exact catalogue increments |
| 2P / 3P range | 2P AC230/400V,AC277/480V orDC80V;3P AC230/400V orAC277/480V;0.5-50A in listed increments |
| Parallel construction | 2PU DC80V:20/30/40/50/60/63/70/80/90/100A;3PU DC80V:105/110/120/125/135/150A. These are parallel-pole single-circuit versions,not independent2/3-pole branches |
| Curves | AC:J2/J4/J6;DC:Z2/Z4/Z6; short/medium/long time respectively |
| Short-circuit basis | DC80V:10kA. AC230/400V:6kA under EN60947-2 but3kA under EN60934/GB17701. AC250V and277/480V:6kA UL1077 with U1 marking; do not treat all as one rating standard |
| Mounting / wiring | 35mm DIN or mini rail;0.5-25mm2 standard,parallel2pole up to35mm2,parallel3pole up to70mm2 |
| Endurance | 10000 mechanical,6000 electrical operations per original table |
| Order suffix | 45mm/57mm operating-face height,auxiliaries,neutral poles and certification suffix require the exact supplied reference; no complete suffix is invented |
The short-circuit reference is conditional on the stated standard and voltage,not an interchangeable6/10kA option. The original full rating,curve and dimension images remain available. The physical parallel-pole arrangements are identified explicitly.
Typical applications
- Electrical panel assembly and installation
Open technical reference image