NewTrend · Tmax
Product overview
NewTrend Tmax-style electronic molded-case circuit breakers. Select an exact frame rating and pole count; rated current, trip unit and voltage-specific Icu follow that version.
Technical selection summary
| Parameter | Specification |
|---|---|
| Published versions | Electronic T4-T7, fixed construction; only combinations listed by the version selector |
| Current definition | Rated uninterrupted current; protection settings depend on the electronic trip unit |
| Rated operating voltage | AC up to 690V, 50/60Hz; Icu values below are specifically at AC380/400/415V |
| Icu / Ics at AC380-415V | T4/T5 N/S/H/L/V: 36/50/70/120/200kA, Ics100%; T6 N/S/H/L/V: 36/50/70/100/150kA, Ics100/100/100/75/75%; T7 S/H/L/V: 50/70/120/150kA, Ics100% |
| Insulation / impulse | Ui1000V; Uimp8kV |
| Electronic releases | T4-T6 PR222DS reference; T7 PR331/P or PR332/P reference. Confirm protection functions and setting range for the actual supply |
| Certification | CE; no ABB, UL, CSA or other original-brand certification claim |
NewTrend supply. Tmax-style names are configuration references; this is not an ABB product. CE only; original-brand approvals are not transferred. The selected hint is an enquiry configuration, not an ABB catalogue number. AC distribution only; exact protection settings and installation accessories must match the order. Published scope excludes unverified lower-current trip combinations and DC wiring.
| Fixed frame | 3P / 4P width mm | Height mm | Depth mm |
|---|---|---|---|
| T4 | 105 / 140 | 205 | 103.5 |
| T5 | 140 / 186 | 205 | 103.5 |
| T6 | 210 / 280 | 268 | 103.5 |
| T7 | 210 / 280 | 268 | 154 manual / 178 motorisable |
Typical applications
- Low-voltage distribution and control applications
Specify your enquiry
For a focused quotation, include:
- Selected model and configuration
- Quantity, installation requirements and destination
- Required supporting documents for the exact configuration
Open technical reference image