People Electric · Moulded Case Circuit Breaker
Product overview
People Electric RDM8HU is a three-pole moulded-case circuit-breaker series for higher-voltage AC distribution systems. Five frame sizes cover the stated rated-current combinations. M and H breaking levels have separate Icu/Ics ratings at AC800V, AC1000V and AC1140V.
Technical selection summary
| Manufacturer / series | Original People Electric RDM8HU |
|---|---|
| Main circuit | AC800V, AC1000V or AC1140V; 50/60Hz; 3P |
| 250A frame currents offered | 63, 80, 100, 125, 140, 160, 200, 225, 250A |
| 315A frame currents | 280, 300, 315A |
| 400A frame currents | 250, 315, 350, 400A |
| 630A frame currents | 400, 500, 630A |
| 800A frame currents | 630, 700, 800A |
| Icu at AC800 / 1000 / 1140V | M: 36.5 / 20 / 10kA; H: 50 / 20 / 15kA |
| Ics at AC800 / 1000 / 1140V, 250/315 frames | M: 25 / 12 / 10kA; H: 35 / 15 / 15kA |
| Ics at AC800 / 1000 / 1140V, 400/630/800 frames | M: 25 / 12 / 10kA; H: 37.5 / 15 / 15kA |
| Insulation / impulse withstand | Ui 1500V; Uimp 12kV |
| Release configuration | Thermal-magnetic distribution protection; confirm complete release and accessory code |
| Reference ambient / altitude | 40°C; altitude ≤2,000m; −5 to +40°C normal conditions |
| Installation | Vertical or horizontal; front or rear connection subject to the ordered construction. Confirm dimensions with the required arc covers and terminals. |
| Optional shunt-release supplies | DC24V, AC230V or AC400V; specify accessory code |
Select the actual operating voltage before checking breaking capacity. Rated current and frame are paired; settings and accessory codes are confirmed separately. Motor-protection duty requires its specified release configuration. Mounting approval must use the exact manufacturer drawing with the required terminal covers and clearances.
Typical applications
- AC distribution at 800V, 1000V or 1140V, subject to coordination with the stated fault-current ratings.
Specify your enquiry
For a focused quotation, include:
- Frame/rated current, M/H level, actual AC voltage, frequency and prospective fault current.
- Distribution or motor duty, trip specification, auxiliary supplies and operating mechanism.
- Front/rear connection, terminal covers, mounting drawing, quantity and destination.
Download People Electric RDM8HU catalogue (PDF)