NewTrend · DZ47-125Z
Product overview
NewTrend DZ47-125Z DC miniature circuit breakers in the verified1P/2P80-125A scope. Poles determine the maximum rated DC voltage.
Technical selection summary
| Parameter | Specification |
|---|---|
| Verified pole / voltage pairing | 1P:DC250V;2P:DC500V |
| Rated current | 80,100,125A per exact original table |
| Breaking capacity | 10kA per actual1P/2P DC nameplates;the generic6/10kA list is not selectable |
| Characteristic | C type;original text gives inconsistent instantaneous multiples,so no unverified multiplier is promoted |
| Impulse / dielectric references | Uimp4kV;AC2kV1minute test per original technical text |
| Installation | 35mm DIN rail,IP20;ambient-5 to+40C,24hour average<=35C |
| Endurance | Electrical>1500;mechanical20000 operations per original sheet |
| Terminals | 25mm2 mechanical capacity;2.0Nm tightening reference;conductor ampacity must be selected separately |
| Scope restriction | 3P/4P higher-DC schemes require their own polarity/series wiring and are outside this verified selectable subset |
The current-specific photographs carry the DC10kA rating and polarity marks. Follow the exact unit markings;AC frequency does not apply to DC circuits. Do not use an unverified3P/4P series arrangement to infer a higher DC rating.
Typical applications
- Electrical panel assembly and installation
Open technical reference image