NewTrend · DW45
Product overview
NewTrend DW45 intelligent air circuit breakers. Select the frame and voltage first; supported current and short-circuit ratings follow the exact original table.
Technical selection summary
| Parameter | Specification |
|---|---|
| Frames / currents | 2000:630/800/1000/1250/1600/2000A;3200:2000/2500/2900/3200A;4000:3200/3600/4000A;6300:4000/5000/6300A |
| Voltage / frequency | AC400V orAC690V;50/60Hz;Ui1000V;Uimp8kV |
| Icu / Ics / Icw at AC400V | Frame2000:80/50/50kA;3200:100/65/65kA;4000:100/65/65kA;6300:120/80/85kA |
| Icu / Ics / Icw at AC690V | Frame2000:50/40/40kA;3200:65/50/50kA;4000:65/50/50kA;6300:80/70/65kA |
| Poles / construction | 3P or4P;fixed or drawout; neutral50% standard,100% separately specified |
| Controller reference | L basic;M standard;H communication type; confirm exact protection settings and communication interface |
| Electrical endurance | Frame2000:1000;3200/4000/6300:500 operations |
| Mechanical endurance without / with maintenance | 2000/3200/4000:2500/10000;6300:2000/8000 |
| Control / mechanism supply | Specify undervoltage, shunt-trip and charging-motor supplies separately; no unsupported coil-voltage matrix is selectable |
The original table transposes the Icu/Ics abbreviations: ultimate means Icu and service means Ics. Values above retain the corresponding full-word rows. Control supplies and accessory suffixes require an exact order specification; do not confuse them with main-circuit voltage. The confirmed scope is AC400/690V.
| Frame / Voltage | Icu | Ics | Icw |
|---|---|---|---|
| 2000 / AC400V | 80kA | 50kA | 50kA |
| 2000 / AC690V | 50kA | 40kA | 40kA |
| 3200 / AC400V | 100kA | 65kA | 65kA |
| 3200 / AC690V | 65kA | 50kA | 50kA |
| 4000 / AC400V | 100kA | 65kA | 65kA |
| 4000 / AC690V | 65kA | 50kA | 50kA |
| 6300 / AC400V | 120kA | 80kA | 85kA |
| 6300 / AC690V | 80kA | 70kA | 65kA |