CHINT · Online motor soft starter
Product overview
CHINT NJR2-ZX online soft starters control three-phase squirrel-cage induction motors. This page focuses on 30–75 kW selections; match the complete ZX model and motor nameplate current.
Technical selection summary
| Architecture | The exact ZX manual describes online thyristor operation without a bypass contactor in the basic unit. Special cabinet or bypass arrangements require their own matching instructions. |
|---|---|
| Page-specific motor power / starter current | NJR2-30ZX: 30 kW / 57 A; NJR2-37ZX: 37 kW / 70 A; NJR2-45ZX: 45 kW / 84 A; NJR2-55ZX: 55 kW / 103 A; NJR2-75ZX: 75 kW / 140 A. These are paired manufacturer table entries, not freely interchangeable power/current options. |
| Supply reference | The exact ZX manual states three-phase AC 380 V ±15% and 50 Hz. A 60 Hz application needs a matching supplied-unit document; do not substitute a broader family catalogue frequency entry. |
| Installation and duty | Install vertically and maintain the manual cooling clearances. Match starting frequency, load torque, ambient conditions and derating to the exact starter and motor. |
The manufacturer manual covers the broader 7.5–75 kW NJR2-ZX family; this listing remains limited to the selected 30–75 kW range. NJR2-T and NJR2-D are different constructions. Match the full ZX code, motor current, supply and starting duty.
Typical applications
- Controlled starting of compatible three-phase AC motors.
- Motor-control assemblies selected by motor current, starting duty and ZX configuration.
CHINT NJR2-ZX 30–75 kW manufacturer reference (PDF)