DELIXI ELECTRIC · XJ3
Product overview
DELIXI XJ3 monitors three-phase motor-control circuits for phase loss and incorrect phase sequence. Select the exact G, 5 or 2 version.
Technical selection summary
| Supply | Three-phase AC380V; 50/60Hz |
|---|---|
| G / 5 protection | Phase loss, phase sequence and 7–10% three-phase voltage imbalance in the 2025 manual |
| XJ3-2 boundary | Its phase-loss protection is effective at motor starting; it is not presented as running phase-loss protection |
| Contacts | 1NO+1NC; AC220V3A resistive in the manual |
| AC-15 working ratings | AC380V0.95A; AC240V1.5A; AC120V3A; Ith5A is separate |
| Dimensions / mounting | XJ3-G/5: 93×45.5×85mm max; XJ3-2: 106×45.5×85mm max; screw or 35mm rail |
| Wiring | Use the original terminal diagram and the specified AC380V contactor coil |
The photograph illustrates XJ3-G. Select the exact protection version; XJ9 and adjustable XJ3-D are separate products. The 2025 manual governs the G/5 imbalance value.
Typical applications
- DELIXI XJ3 monitors three-phase motor-control circuits for phase loss and incorrect phase sequence.