The delay setting mechanism of this series of products is easy to operate and has appropriate operating force. When the potentiometer rotates, it feels smooth and has appropriate strength and rotational torque
| product name | Delay type | Delay Time | Rated control power supply voltage |
| JSZ3 | |||
| A: Power on delay, delay 2 conversion C: Power on delay, delay 1 conversion Instantaneous 1 conversion F: Power outage delay K: Disconnect delay Y: Star Triangle Conversion R: Loop delay |
A:0.5s/5s/30s/3min B:1s/10s/60s/6min C:5s/50s/5min/30min D:10s/100s/10min/60min E:60s/10min/60min/6h F:2min/20min/2h/12h G:4min/40min/4h/24h 1S:0.1s~1s 2S:0.2s~2s … 60M:6min~60min … |
12:AC12V … 380:AC380V 12D:DC12V … 220D:DC220V |
Note: JSZ3A delay time is only used for 0.5s/5s/30s/3min. 1s/10s/60s/6min. 5s/50s/5min/30min
10s/100s/10min/60min 60s/10min/60min/6h 2min/20min/2h/12h 4mm/40min/4h/24h
This product can replace the original JSZ3-2 product
JSZ3C delay time is only used for 0.5s/5s/30s/3min. 1s/10s/60s/6min. 5s/50s/5min/30min
10s/100s/10min/60min 60s/10min/60min/6h 2min/20min/2h/12h 4mm/40min/4h/24h
This product can replace the original JSZ3-3 product
JSZ3F delay time is only used for 0.1s-1s. 0.2s-2s. 0.3s-3s. 0.5s-5s. 0.5s-6s. 1s-10s
2s-20s. 2. 5s-30s 5s-60s 10s-100s 10s-120s 10s-180s 0.4min-4min. 0.5mmin-5min
0.5min-6min, 1min-10min, 2min-20min, 2.5min-30min
JSZ3K delay time is only used for 0.1s-1s. 0.2s-2s. 0.3s-3s. 0.5s-5s. 0.5s-6s, 1s-10s
2s-20s 2. 5s-30s 5s-60s 10s-100s, 10s-120s 10s-180s 0.4min-4min. 0.5mmin-5min
0.5min-6min, 1min-10min, 2min-20min 2.5min-30min. 5min-60min
The JSZ3Y delay time is only used for 0.1s-1s. 0.2s-2s. 0.3s-3s. 0.5s-5s. 1s-10s 2. 5s-30s 5s-60s 0s-120s
10s-180s. 0.5min-5min, 1min-10min
The JSZ3R delay time is only used for 0.5s-6s-60s. 1s-10s/10min. 2.5s-30s/30min. 1s-10s/100s
2.5s-30s/min. 60S-10min./100min
Product parameters
| AC-15 | Ue | V | 380(AC) | 240 (AC) | 120(AC) |
| le | A | 0.95 | 1.5 | 3 | |
| DC-13 | Ue | V | 250(DC) | 125(DC) | |
| le | A | 0.27 | 0.55 | ||
| Conventional thermal current | A | 5 | |||
| repetitive error | ≤5% | ||||
| mechanical life | order | ≥1×10⁶ | |||
| Electrical life | order | ≥1×10⁵ | |||
| consumption | W | ≤3 | |||
| Rated control power supply voltage | V | 12~380(AC) | |||
| V | 12~220(DC) | ||||
| international standard | EC 60947-5-1 | ||||
| national standard | GB/T 14048.5 | ||||
| authentication certificate | CCC | ||||