NewTrend · BRCCB
Product overview
NewTrend BRCCB Type B residual-current circuit breakers for applications needing documented DC-sensitive residual-current protection. Select poles, current and sensitivity.
Technical selection summary
| Parameter | Specification |
|---|---|
| Function | RCCB residual-current protection without integral overcurrent protection |
| Poles / voltage | 2P(1P+N):240V;4P(3P+N):415V;50/60Hz per original source matrix |
| Rated current | 25/40/63A |
| Sensitivity | 30/100/300mA; residual non-operating reference0.5IΔn |
| Residual response | Type B; pulsating and smooth DC response and frequency-dependent limits retained in full source tables |
| Conditional short circuit | Inc/IΔc10kA with coordinated upstream short-circuit protective device; not standalone MCB breaking capacity |
| Installation | 35mm DIN rail, vertical,≤25mm² conductor,2.0Nm,IP20 |
| Endurance | 4000 electromechanical operations per supplier table |
Type B describes residual-current response, not an overcurrent trip curve. No C curve or independent6kA breaker rating is claimed. The retained240/415V printed matrix governs this supply;230/400V nominal system references do not create extra product versions.
Typical applications
- Residual-current protection in circuits requiring Type B response
Open technical reference image