NewTrend · F360
Product overview
NewTrend F360 type AC residual-current circuit breakers. Pole count controls the available rated-current and residual-current options.
Technical selection summary
| Parameter | Specification |
|---|---|
| 2P F362 | 16,25,32,40,63A; 10/30/100/300mA; AC220/240V |
| 4P F364 | 25,32,40,63,100A; 30/100/300mA; AC220/380V or240/415V |
| Residual-current type | AC, confirmed actual supply |
| Frequency | 50/60Hz |
| RCCB function | Residual-current protection; no integral overcurrent protection |
| Dimensions | 2P width35.7mm; 4P width71.5mm; height81mm; depth73.8mm (drawing tolerances retained) |
| Environment / life | -5 to +55C; at least10,000 operations per supplied table |
Provide separate coordinated short-circuit and overload protection. Do not treat the former 6kA/C-curve fields as an RCCB interrupting rating. The old timing row is ambiguous and is not a universal trip-time claim; confirm the exact residual-current test conditions.
Typical applications
- Low-voltage distribution and control applications
Open technical reference image