Technical selection summary
| Series | DZ47LE; confirm complete suffix |
|---|---|
| Current options currently listed | 80 A, 100 A and 125 A; confirm exact version |
| Residual-current options currently listed | 30 mA, 100 mA or 300 mA |
| Pole arrangement | Confirm 1P+N, 2P, 3P, 3P+N or 4P by wiring diagram |
| Protection configuration | Confirm integrated overload / short-circuit protection and applicable standard |
DZ47LE-100 and DZ47LE-125 are different configurations. Ratings must match the exact suffix. Obtain the complete model and nameplate before confirming rated voltage, current or fault rating.
Typical applications
- AC distribution procurement by exact configuration
- Replacement matching the existing wiring arrangement
- OEM protection assemblies
Product reference images and drawings
Compare the exact model, voltage and duty. Reference tables may include other frames or versions; confirm the ordered configuration before using any rating or dimension.
Model comparison
| Type | DZ47LE-125 | |
| Pole | 1P+N, 2P | 3P, 3P+N, 4P |
| Rated current (A) | 63,80,100,125 | |
| Rated voltage(V) | 230 | 400 |
| Rated short circuit breaking capacity Icn(KA) | 6 | |
| Rated residual making/breaking capacity Im(A) | 2000 | |
| Rated residual action current In(A) | 0.03,0.1,0.3 | |
| Rated residual non-action current Ino(A) | 0.5In | |
| Over voltage protection grade | 280V±5% | |
Additional technical data 2
| Rated current(A) | 63 | 80 | 100 |
| Nominal cross section of wire mm2 | 16 | 25 | 35 |
Additional technical data 3
| In(A) | In(A) | Breaking time(s) when equals to rating following | ||||
| In | 2In | 5In | 5,10,20,50,100,200,500a(A) | Itb | ||
| 6-63 | 0.03, 0.05, 0.1, 0.3 | 0.1 | 0.06 | 0.04 | 0.04 | 0.04 |
Additional technical data 4
| Ambient Temperature | Initial Status | Test Current | Expected Result | Expected Result | NOte |
| 40±2oC | Cold position | 1.05In(In≤63A) | t≤1h | Non-release | – |
| Cold position | 1.05In (In[63A) | t≤2h | Non-release | – | |
| Carried out immedi-ately after previous test | 1.30In(In≤63A) | t < 1h | Release | Current smoothlyrises to specified value within 5s | |
| 1.30In (In>63A) | t< 2h | Release | |||
| -5~+40oC | Cold position | 8.00In | t≤0.2s | Non-release | – |
| Cold position | 12.00In | t < 0.2s | Non-release | – |