NewTrend · NTL11-63
Product overview
NewTrend NTL11-63 one-module RCBOs with linked phase and switched-neutral operation. Select current,curve,residual type and sensitivity.
Technical selection summary
| Parameter | Specification |
|---|---|
| Actual breaking rating | 6kA, confirmed by supplier-owner;not a selectable10kA version |
| Construction | Electronic RCBO;1protected pole plus switched neutral |
| Rated current | 6,10,16,20,25,32,40,50,63A |
| Residual protection | AC orA type;30/100/300mA;instantaneous type |
| Main supply | AC240V,50/60Hz per original technical sheet |
| Curves | B orC per original characteristic curves |
| Outline | 18mm module width,123mm overall height,78.6mm depth per original drawing |
| Connection | Use L/N IN/OUT and FE marking in exact original wiring diagram;do not use the device outside the prescribed supply direction |
| Terminal capacity | Rigid conductor25mm2 mechanical reference;size conductor by actual load and installation rules |
| Endurance | 4000electro-mechanical cycles per original sheet |
The supplier confirmed6kA for the actual supply;the former10kA headline is removed. Main photo shows a representative current/sensitivity,not every available configuration. Test and protective-earth/function-earth connections must follow the exact device instructions.
Typical applications
- Electrical panel assembly and installation
Open technical reference image