DELIXI ELECTRIC · HR17
Product overview
DELIXI HR17 combines isolation and fuse protection. Select frame thermal current, poles, circuit voltage and auxiliary contacts for the standard mounting version.
Technical selection summary
| Thermal-current sizes | 32/63/100A in100 frame; 160/250/400/630/800A in corresponding frames |
|---|---|
| Poles | 100 frame: 2P/3P; larger frames: 3P |
| Voltage / duty | AC400V: AC-23B; AC690V: AC-22B for100 frame and AC-21B for160–800 frames in the 2025 manual |
| Insulation | Ui800V for100 frame; Ui1000V for larger frames; Uimp8kV |
| Fuse size matching | 100:RT16-000; 160:RT16-00; 250:RT16-1; 400:RT16-2; 630:RT16-3; 800:RT16-3C |
| Current definition | The selected Ith is frame thermal current. Working-current and fuse duty must match the circuit utilization category and actual marking |
This page follows the 2025 HR17 standard-mounted manual. Thermal current is not labelled as a universal motor-switching current. Select the listed fuse and duty; the withdrawn HR17-M busbar construction is outside this selection.
Typical applications
- DELIXI HR17 combines isolation and fuse protection.