Product overview
JD-5E detects motor overload and phase failure through its current-sensing arrangement. Select a setting window containing the motor rated current, then coordinate its output with the motor contactor and upstream short-circuit protection.
Technical selection summary
| Series | JD-5E |
|---|---|
| Protection | Overload and phase failure |
| Current setting windows | 1–5A, 5–25A, 20–80A, 80–200A, 160–400A |
| Control circuit | AC 220 V or AC 380 V as specified in the wiring diagrams |
| Selection note | Match the current window to the motor nameplate and the specified feed-through wiring. |
| Model-specific protection-class reference | The CHINT JD-5E catalogue lists IP00 for JD-5E/5, /25 and /80, and IP20 for JD-5E/200 and /400 (enclosure protection class, where applicable). Match the complete model; neither entry is a sealed or waterproof rating |
| Manufacturer operating-principle reference | The CHINT JD-5E catalogue, section 4.1.1, describes a three-phase electronic motor protector. Motor-current sensing and overload/phase-failure protection are separate from the control-contact output; select the complete model and output arrangement |
Match the current window to the motor nameplate and the specified feed-through wiring.
Typical applications
- Pump and fan control panels
- Fixed-direction motor starters
- Motor overload and phase-failure monitoring