DELIXI ELECTRIC · CDB9NTC / CDB9HTC
Product overview
DELIXI CDB9NTC and CDB9HTC provide overload, short-circuit protection and isolation. Select6kA NTC or 10kA HTC, current, poles and C/D characteristic.
Technical selection summary
| Current options | 1A, 2A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A |
|---|---|
| Model / capacity | CDB9NTC:6kA; CDB9HTC:10kA |
| AC scope | AC230/400V; 1P, 2P, 3P, 4P; match actual pole wiring |
| Instantaneous setting | C:8In±20%; D:12In±20% in the current TC catalogue |
| Standard | GB/T14048.2; IEC/EN60947-2 |
| Terminals / mounting | 25mm²; 2.5N·m; 35mm DIN rail |
Selection follows the2023-10-20 TC catalogue for the specified AC scope. Use the exact NTC6kA or HTC10kA build; confirm any DC application against its complete factory version. Ordinary CDB9N/H and TC variants remain distinct.
Typical applications
- Electrical distribution or control circuits within the selected manufacturer ratings.