DELIXI ELECTRIC · CDB6HTC-63
Product overview
DELIXI CDB6HTC-63 provides thermal-magnetic overload and short-circuit protection. Choose poles, the linked AC or DC operating voltage, rated current and tripping characteristic.
Technical selection summary
| Rated currents | 1A, 2A, 3A, 4A, 5A, 6A, 8A, 10A, 13A, 16A, 20A, 25A, 32A, 40A, 50A, 63A |
|---|---|
| Poles / operating voltage | 1P: AC230/240V or DC80V; 2P: AC400/415V or DC125V; 3P and 4P: AC400/415V only |
| Frequency | 50/60Hz for AC circuits |
| Breaking capacity | Icu6kA; Ics=100%Icu in the exact manufacturer manual |
| Instantaneous setting | AC: B4In, C8In, D12In; DC: B5In, C10In, D15In. These are fixed characteristics, not adjustable settings |
| Product standard | GB/T14048.2; use the industrial-breaker characteristics in the attached manual |
| Installation / terminals | TH35-7.5 rail; 2.0N·m terminal torque; use the current-specific conductor sizes and actual pole wiring |
| Selection reference | The displayed hint identifies this configuration; confirm the complete factory marking when ordering |
Match the selected pole and circuit-voltage pair to the manufacturer wiring diagram. The DC80V and DC125V ratings apply only to 1P and 2P respectively. Select the correct AC/DC instantaneous characteristic; do not apply another CDB6 model’s curve or infer higher DC voltages by adding poles.
Typical applications
- DELIXI CDB6HTC-63 provides thermal-magnetic overload and short-circuit protection.