CHINT · Residual current circuit breaker
Product overview
The CHINT NL210 Type B is an RCCB without integral overcurrent protection. Its Type B residual-current function covers sinusoidal AC, pulsating DC and smooth DC residual currents within the manufacturer conditions.
Technical selection summary
| Construction / poles | 2P / 4P; RCCB without overload or short-circuit trip protection |
|---|---|
| Rated current | 25, 40 or 63 A |
| Rated voltage / frequency | 2P: AC 230/240 V; 4P: AC 400/415 V; 50 Hz |
| Residual sensitivity | 30, 100 or 300 mA; choose the appropriate protection and selectivity requirement |
| Waveform selection | Type B, including the documented residual-current frequency response up to 1000 Hz; not a 1000 Hz supply rating |
| Conditional short-circuit current | Inc / IΔc: 10 kA with the specified coordinated upstream short-circuit protective device |
| Installation / standard | 35 mm DIN rail; IEC/EN 62423 and IEC/EN 61008-1 manufacturer references |
The 10 kA conditional rating is not an independent MCB/MCCB interrupting rating. Provide coordinated overcurrent protection. For EV charging, PV converters or drives, verify the equipment leakage waveform, DC component, earthing and installation rules; Type B alone does not establish compatibility with every system or satisfy every required protective function.
Typical applications
- Distribution circuits requiring Type B residual-current detection
- Converter, drive or EV-charging installations after system compatibility checks
Product reference images and drawings
Match the exact model, suffix, electrical duty and mounting arrangement. The retained family references may show other versions; use the applicable manufacturer row and drawing for the ordered unit.