NewTrend · ELR-3C
Product overview
NewTrend ELR-3C residual-current monitoring relay for a matched external toroidal sensor. Select the exact supply version and required current/time setting ranges.
Technical selection summary
| Parameter | Specification |
|---|---|
| Power versions | Separate12V,24/48V and110V AC/DC plus230/400V AC versions;not one universal-supply device |
| Frequency / consumption | 50/60Hz forAC;maximum3VA |
| Residual-current setting | 0.025-0.25A(K0.1),0.25-2.5A(K1),2.5-25A(K10);25-250A needs external multiplier and is not selected here |
| Delay setting | 0.02-0.5s or0.2-5s with time multiplier |
| Output rating | One changeover contact,5A250V;not a25A load-switching relay |
| Supply terminals | 12V version:7-5;24/48V version:7-5 for24V,7-3 for48V;standard version:7-5 for110V,7-3 for mains low tap,7-1 for mains high tap |
| Important terminal condition | Reference drawing marks mains taps220/380V while its table uses230/400V with tolerance. Follow the actual nameplate. The same7-5 terminal pair has different voltages on different versions |
| External toroid | Use matched sensor;lead continuity supervision,tripping on interrupted toroid circuit;do not treat an arbitraryCT ratio as compatible |
| Reset / test | Manual or automatic reset selection,test pushbutton and remote test |
| Outline | 52.5 x85 x73mm;35mm DIN rail,three modules |
| Wiring / environment | 2.5mm2 screw terminals;IP20;-10 to+60C operating,-20 to+80C storage,relative humiditybelow90% |
| Insulation | 2.5kV for60s per reference manual |
The supply choices are alternative hardware versions. Terminal7-5 is not universally12V,24V or110V. Check the supplied label before energising. NewTrend supply does not inherit Contrel or other original-brand approvals. The matched toroid must be specified in the quotation.
Typical applications
- Electrical panel assembly and installation