NewTrend / OEM · HRC fuse link and base
Product overview
The fuse table compares link and base models, currents, voltage-specific entries, losses and weights.
Technical selection summary
| Listing / reference model | NH / NT / RT16 references |
|---|---|
| Product type | HRC fuse link and base |
Keep fuse-link and fuse-base ratings separate. The source cross-references require the exact physical size and manufacturer drawing rather than assumed universal interchangeability. Confirm utilisation class, voltage, AC/DC duty and protective coordination for the selected row. Select the fuse-link size and utilization category separately from the base. Match AC/DC voltage, current, power loss, striker/indicator and backup-protection requirements; a base does not establish the fuse-link breaking capacity.
Model-specific reference data
Use the matching model and version in the reference data. Confirm the applicable rating, test conditions and dimensions against the exact supplied unit.
| Type | Fuse link | Fuse base | |||||
|---|---|---|---|---|---|---|---|
| Rated current (A) | Rated voltage (V) | Rated power loss (W) | Weight (kg) | Type | Rated current (A) | Weight (kg) | |
NT00C NH00C RT16-000 | 2 | 500, 600 | 0.41 | 0.15 | Sist 101 | 160 | 0.2 |
| 4 | 0.62 | ||||||
| 6 | 0.81 | ||||||
| 10 | 1.08 | ||||||
| 16 | 1.60 | ||||||
| 20 | 1.81 | ||||||
| 25 | 2.31 | ||||||
| 32 | 3.07 | ||||||
| 36 | 3.17 | ||||||
| 40 | 4.05 | ||||||
| 50 | 4.25 | ||||||
| 63 | 4.70 | ||||||
| 80 | 5.7 | ||||||
| 100 | 7 | ||||||
NT00 NH00 RT16-00 | 4 | 500, 600 | 0.67 | 0.15 | Sist 101 | 160 | 0.2 |
| 6 | 0.89 | ||||||
| 10 | 1.14 | ||||||
| 16 | 1.65 | ||||||
| 20 | 1.94 | ||||||
| 25 | 2.50 | ||||||
| 32 | 3.32 | ||||||
| 36 | 3.56 | ||||||
| 40 | 4.30 | ||||||
| 50 | 4.5 | ||||||
| 63 | 4.6 | ||||||
| 80 | 6 | ||||||
| 100 | 7.3 | ||||||
| 125 | 500 | 7.6 | |||||
| 160 | 9.6 | ||||||
NT0 NH0 RT16-0 | 6 | 500, 600 | 1.03 | 0.2 | Sist 160 | 160 | 0.32 |
| 10 | 1.42 | ||||||
| 16 | 2.45 | ||||||
| 20 | 2.36 | ||||||
| 25 | 2.7 | ||||||
| 32 | 3.74 | ||||||
| 35 | 4.3 | ||||||
| 40 | 4.7 | ||||||
| 50 | 5.5 | ||||||
| 63 | 6.9 | ||||||
| 80 | 7.6 | ||||||
| 100 | 8.9 | ||||||
| 125 | 500 | 10.1 | |||||
| 160 | 15.2 | ||||||
| Type | Fuse link | Fuse base | |||||
|---|---|---|---|---|---|---|---|
| Rated current (A) | Rated voltage (V) | Rated power loss (W) | Weight (kg) | Type | Rated current (A) | Weight (kg) | |
NT1 NH1 RT16-1 | 80 | 500, 600 | 6.2 | 0.36 | Sist 201 | 250 | 0.8 |
| 100 | 7.5 | ||||||
| 125 | 10.2 | ||||||
| 160 | 13 | ||||||
| 200 | 15.2 | ||||||
| 224 | 500 | 16.8 | |||||
| 250 | 18.3 | ||||||
NT2 NH2 RT16-2 | 125 | 500, 600 | 9 | 0.65 | Sist401 | 400 | 1.2 |
| 160 | 11.5 | ||||||
| 200 | 15 | ||||||
| 224 | 16.6 | ||||||
| 250 | 18.4 | ||||||
| 300 | 21 | ||||||
| 315 | 19.2 | ||||||
| 355 | 24.5 | ||||||
| 400 | 26 | ||||||
NT3 NH3 RT16-3 | 315 | 500, 600 | 21.7 | 0.85 | Sist601 | 630 | 1.5 |
| 355 | 22.7 | ||||||
| 400 | 26.8 | ||||||
| 425 | 28.9 | ||||||
| 500 | 500 | 32 | |||||
| 630 | 40.3 | ||||||
NT4 NH4 RT16-4 | 800 | 380 | 62 | 1.95 | Sist1001 | 1000 | 3.45 |
| 1000 | 75 | ||||||
NewTrend · NT4 gG
NT4 1250A ceramic knife-blade fuse
NT4 is a ceramic knife-blade gG fuse link for low-voltage general-purpose circuit protection. The illustrated 1250A configuration is marked 120kA at 500V AC and 50kA at 690V AC. Select a mechanically and electrically compatible mounting assembly for this fuse link.
NT4 1250A technical selection summary
| Model | NT4 |
|---|---|
| Illustrated rated current | 1250A |
| Published series current range | 500-1250A |
| Operating class | gG |
| AC voltage / breaking capacity | 500V AC / 120kA; 690V AC / 50kA |
| Standard marking | IEC 60269 |
| Insulating body | Ceramic |
| Connection | Knife-blade contacts |
Protection and mounting coordination
The gG utilisation category provides full-range overload and short-circuit protection for general-purpose circuits. Match 1250A to the circuit and use the voltage-specific breaking capacity: 120kA at 500V AC or 50kA at 690V AC. Confirm electrical and mechanical compatibility of the mounting assembly independently. Fuse link and base are specified separately.
Match the 200mm overall length and 97 x 113mm end-view envelope.
Product views and original rating markings



NT4 dimensions in millimetres

| Overall blade-tip length | 200mm |
|---|---|
| Body axial length | 90mm |
| End-view width | 97mm |
| End-view overall height | 113mm |
Materials and applications

NH00 160A gG reference
NH00 160A is a gG knife-contact HRC fuse link for compatible low-voltage industrial and commercial protection assemblies. The illustrated unit is marked 500V AC / 120kA and 690V AC / 50kA. Select the voltage-specific breaking capacity and matching holder geometry together.
| Physical model | NH00 |
|---|---|
| Rated current | 160A |
| Operating class | gG |
| AC configuration 1 | 500V AC / 120kA |
| AC configuration 2 | 690V AC / 50kA |
| Standard marking | IEC 60269 |
| Contact type | Knife contacts |
Selection and application
For overload and short-circuit protection in compatible low-voltage circuits. The 120kA rating applies at 500V AC; the 50kA rating applies at 690V AC. This reference covers the exact illustrated 160A unit. Confirm holder contact geometry and required indication arrangement for the installation.

Dimensions in millimetres

| A | 78mm |
|---|---|
| B | 53mm |
| C | 15mm |
| D | 30mm |
| H | 60mm |
NT00C 63A gG reference
NT00C 63A is a gG knife-contact HRC fuse link for compatible low-voltage industrial and commercial protection assemblies. The illustrated unit is marked 500V AC / 120kA and 690V AC / 50kA. Select the voltage-specific breaking capacity and matching holder geometry together.
| Physical model | NT00C |
|---|---|
| Rated current | 63A |
| Operating class | gG |
| AC configuration 1 | 500V AC / 120kA |
| AC configuration 2 | 690V AC / 50kA |
| Standard marking | IEC 60269 |
| Contact type | Knife contacts |
Selection and application
For overload and short-circuit protection in compatible low-voltage circuits. The 120kA rating applies at 500V AC; the 50kA rating applies at 690V AC. This reference covers the exact illustrated 63A unit. Confirm holder contact geometry and required indication arrangement for the installation.

Dimensions in millimetres

| A | 78mm |
|---|---|
| B | 52mm |
| C | 15mm |
| D | 21mm |
| H | 53mm |
NewTrend · NT0
NT0 160A gG Fuse Link, 500V / 690V AC
NT0 is a 160A knife-blade gG fuse link for general-purpose low-voltage circuit protection. The illustrated unit is marked 500V AC at 120kA, 690V AC at 50kA and IEC 60269. Its dedicated dimensional reference specifies a 125mm overall length, 68mm body reference length and 15mm blade width.
Technical selection summary
| Model | NT0 |
|---|---|
| Rated current | 160A |
| Rated voltage | 500V AC / 690V AC |
| Breaking capacity at 500V AC | 120kA |
| Breaking capacity at 690V AC | 50kA |
| Operating class | gG |
| Standard marking | IEC 60269 |
| Terminal type | Knife-blade contacts |
Applications and selection
For compatible industrial distribution and equipment-protection circuits. Match fuse current, system voltage and prospective fault current to the protected circuit, and coordinate the fuse with upstream and downstream devices. Use a holder suitable for the exact blade and body dimensions.
Isolate and verify the circuit is de-energized before removing or installing the fuse.
Product construction and markings

Dimensions in millimetres

| Overall length | 125mm |
|---|---|
| Body reference length | 68mm |
| Blade width | 15mm |
| Body width | 29mm |
| End height | 56.5mm |
| Auxiliary slot width | 6mm |
| Upper reference width | 10mm |
| Upper projection | 2.5mm +0.5mm |