People Electric · Rail-Mounted Terminal Block
Product overview
People Electric UK terminal blocks use a box-type screw-clamp connection for electrical control and distribution wiring. The series supports G-type and TH-type mounting rails. Select the complete model using its individual conductor ranges and tabulated ratings, then confirm the rail and installation clearance.
Technical selection summary
| Manufacturer / series | Original People Electric UK |
|---|---|
| Application system stated in introduction | AC660V 50/60Hz or DC440V. The separate model table lists rated-voltage values; these do not extend the stated application-system limits. |
| Connection / mounting | Box-type screw clamp; G-type or TH-type rail, subject to exact assembly |
| Clamp materials | Copper pressure plates and screws through 50mm²; steel pressure plates and screws above 50mm², as stated by manufacturer |
| UK2.5B | Rigid conductor 0.2–4mm²; flexible conductor 0.2–2.5mm²; rated current 32A; table rated voltage 690V; A×B×C=42×42.5×6.2mm |
| UK3N | Rigid conductor 0.2–4mm²; flexible conductor 0.2–2.5mm²; rated current 32A; table rated voltage 800V; A×B×C=47×42.5×5.2mm |
| UK5N | Rigid conductor 0.2–6mm²; flexible conductor 0.2–4mm²; rated current 41A; table rated voltage 800V; A×B×C=47×42.5×6.5mm |
| UK6N | Rigid conductor 0.2–10mm²; flexible conductor 0.2–6mm²; rated current 57A; table rated voltage 800V; A×B×C=47×42.5×8.2mm |
| UK10N | Rigid conductor 0.5–16mm²; flexible conductor 0.5–10mm²; rated current 76A; table rated voltage 800V; A×B×C=47×42.5×10.2mm |
| UK16N | Rigid conductor 2.5–25mm²; flexible conductor 4–16mm²; rated current 101A; table rated voltage 800V; A×B×C=54×42.5×12.2mm |
| UK35 | Rigid conductor 10–35mm²; flexible conductor 10–35mm²; rated current 150A; table rated voltage 1000V; A×B×C=51×55×15.2mm |
| UKH50 | Rigid conductor 16–50mm²; flexible conductor 25–50mm²; rated current 150A; table rated voltage 1000V; A×B×C=83.5×70.5×20mm |
| UKH95 | Rigid conductor 25–95mm²; flexible conductor 35–95mm²; rated current 232A; table rated voltage 1000V; A×B×C=97.5×83×25mm |
| UK150 | Rigid conductor 35–150mm²; flexible conductor 50–150mm²; rated current 309A; table rated voltage 1000V; A×B×C=118.5×100×31mm |
| Standards stated by manufacturer | IEC60947-1 and GB14048; no independent certification claim is made. |
Choose the complete model rather than combining independent current and conductor values. Model-table rated voltages are preserved separately from the introductory AC660V/DC440V system scope. USLKG protective-conductor models in the shared catalogue are a separate family and are not offered as UK models.
Typical applications
- Rail-mounted control and distribution terminal connections.
- Replacement terminal assemblies requiring verified model dimensions and conductor capacities.
Specify your enquiry
For a focused quotation, include:
- Complete UK model and quantity.
- Rigid/flexible copper conductor size, circuit voltage and current.
- G/TH rail details, installation space and required accessories.
Download People Electric UK catalogue (PDF)