People Electric RDAC industrial wiring devices are identified by component type, current code and pole count. Voltage and protective-earth clock position must match the intended mating device. The selectors restrict voltage/clock options to the manufacturer table for the selected complete model; a matching current and pole count alone does not establish compatibility.
Technical selection summary
| Manufacturer / series | Original People Electric RDAC |
|---|---|
| Code structure | First digit: 0 plug, 1 socket, 2 connector, 3 concealed/panel socket. Current code: 1=16A, 2=32A, 3=63A, 4=125A. Last digit: number of poles. |
| Voltage / clock restrictions | 3-pole 16/32A: 110–130V at 4h or 220–250V at 6h. 3-pole 63/125A: 220–250V at 6h only. 4-pole models: 380–415V at 6h. 5-pole models: 220–380 / 240–415V at 6h, exactly as tabulated. |
| Component IP ratings | Plugs/sockets/panel sockets: 16/32A IP44, 63/125A IP67. Connector table lists IP44 for all four current sizes. Confirm the complete mated assembly rating. |
| RDAC-013 | Plug; 16A; 3 poles per code; IP44; 110–130V, 4h or 220–250V, 6h |
| RDAC-014 | Plug; 16A; 4 poles per code; IP44; 380–415V, 6h |
| RDAC-015 | Plug; 16A; 5 poles per code; IP44; 220–380 / 240–415V, 6h |
| RDAC-023 | Plug; 32A; 3 poles per code; IP44; 110–130V, 4h or 220–250V, 6h |
| RDAC-024 | Plug; 32A; 4 poles per code; IP44; 380–415V, 6h |
| RDAC-025 | Plug; 32A; 5 poles per code; IP44; 220–380 / 240–415V, 6h |
| RDAC-033 | Plug; 63A; 3 poles per code; IP67; 220–250V, 6h |
| RDAC-034 | Plug; 63A; 4 poles per code; IP67; 380–415V, 6h |
| RDAC-035 | Plug; 63A; 5 poles per code; IP67; 220–380 / 240–415V, 6h |
| RDAC-043 | Plug; 125A; 3 poles per code; IP67; 220–250V, 6h |
| RDAC-044 | Plug; 125A; 4 poles per code; IP67; 380–415V, 6h |
| RDAC-045 | Plug; 125A; 5 poles per code; IP67; 220–380 / 240–415V, 6h |
| RDAC-113 | Surface socket; 16A; 3 poles per code; IP44; 110–130V, 4h or 220–250V, 6h |
| RDAC-114 | Surface socket; 16A; 4 poles per code; IP44; 380–415V, 6h |
| RDAC-115 | Surface socket; 16A; 5 poles per code; IP44; 220–380 / 240–415V, 6h |
| RDAC-123 | Surface socket; 32A; 3 poles per code; IP44; 110–130V, 4h or 220–250V, 6h |
| RDAC-124 | Surface socket; 32A; 4 poles per code; IP44; 380–415V, 6h |
| RDAC-125 | Surface socket; 32A; 5 poles per code; IP44; 220–380 / 240–415V, 6h |
| RDAC-133 | Surface socket; 63A; 3 poles per code; IP67; 220–250V, 6h |
| RDAC-134 | Surface socket; 63A; 4 poles per code; IP67; 380–415V, 6h |
| RDAC-135 | Surface socket; 63A; 5 poles per code; IP67; 220–380 / 240–415V, 6h |
| RDAC-143 | Surface socket; 125A; 3 poles per code; IP67; 220–250V, 6h |
| RDAC-144 | Surface socket; 125A; 4 poles per code; IP67; 380–415V, 6h |
| RDAC-145 | Surface socket; 125A; 5 poles per code; IP67; 220–380 / 240–415V, 6h |
| RDAC-313 | Panel socket; 16A; 3 poles per code; IP44; 110–130V, 4h or 220–250V, 6h |
| RDAC-314 | Panel socket; 16A; 4 poles per code; IP44; 380–415V, 6h |
| RDAC-315 | Panel socket; 16A; 5 poles per code; IP44; 220–380 / 240–415V, 6h |
| RDAC-323 | Panel socket; 32A; 3 poles per code; IP44; 110–130V, 4h or 220–250V, 6h |
| RDAC-324 | Panel socket; 32A; 4 poles per code; IP44; 380–415V, 6h |
| RDAC-325 | Panel socket; 32A; 5 poles per code; IP44; 220–380 / 240–415V, 6h |
| RDAC-333 | Panel socket; 63A; 3 poles per code; IP67; 220–250V, 6h |
| RDAC-334 | Panel socket; 63A; 4 poles per code; IP67; 380–415V, 6h |
| RDAC-335 | Panel socket; 63A; 5 poles per code; IP67; 220–380 / 240–415V, 6h |
| RDAC-343 | Panel socket; 125A; 3 poles per code; IP67; 220–250V, 6h |
| RDAC-344 | Panel socket; 125A; 4 poles per code; IP67; 380–415V, 6h |
| RDAC-345 | Panel socket; 125A; 5 poles per code; IP67; 220–380 / 240–415V, 6h |
| RDAC-213 | Connector; 16A; 3 poles per code; IP44; 110–130V, 4h or 220–250V, 6h |
| RDAC-214 | Connector; 16A; 4 poles per code; IP44; 380–415V, 6h |
| RDAC-215 | Connector; 16A; 5 poles per code; IP44; 220–380 / 240–415V, 6h |
| RDAC-223 | Connector; 32A; 3 poles per code; IP44; 110–130V, 4h or 220–250V, 6h |
| RDAC-224 | Connector; 32A; 4 poles per code; IP44; 380–415V, 6h |
| RDAC-225 | Connector; 32A; 5 poles per code; IP44; 220–380 / 240–415V, 6h |
| RDAC-233 | Connector; 63A; 3 poles per code; IP44; 220–250V, 6h |
| RDAC-234 | Connector; 63A; 4 poles per code; IP44; 380–415V, 6h |
| RDAC-235 | Connector; 63A; 5 poles per code; IP44; 220–380 / 240–415V, 6h |
| RDAC-243 | Connector; 125A; 3 poles per code; IP44; 220–250V, 6h |
| RDAC-244 | Connector; 125A; 4 poles per code; IP44; 380–415V, 6h |
| RDAC-245 | Connector; 125A; 5 poles per code; IP44; 220–380 / 240–415V, 6h |
| Dimensions | Model-specific a–g drawings and tables are included in the full-width reference images and the complete original PDF. Dimensions are not interchangeable between plugs, sockets, panel sockets and connectors. |
| Image example | Main photo is the original PEOPLE-labelled RDAC-013, 16A, 6h, 220/250V, IP44. Other photos illustrate series members. |
Match complete model, voltage, pole arrangement and clock position on both mating components. The IP rating shown belongs to the individual component table; do not assume an IP67 assembled system when a mating connector is IP44. Confirm cable size, gland, mounting dimensions and required included parts.
Typical applications
- Industrial detachable power connections using matching RDAC wiring devices.
- Machine, cabinet and installation connections requiring the documented component type and clock position.
Specify your enquiry
For a focused quotation, include:
- Complete RDAC model, supported voltage/clock selection and quantity of each mating component.
- Pole arrangement, current, circuit voltage/frequency and desired complete assembly IP rating.
- Cable diameter/cross-section, mounting or gland requirements and destination.