People Electric · Low-Voltage Switchgear Assembly
Product overview
People Electric RMNS integrated low-voltage switchgear provides modular distribution and motor-control functions. Its horizontal and vertical busbar arrangements depend on the selected power-distribution or MCC construction. Quote against an approved circuit and cabinet schedule, with the exact protection and ventilation design confirmed.
Technical selection summary
| Manufacturer / series | Original People Electric RMNS |
|---|---|
| Rated operating / insulation voltage | AC380V or AC660V; rated insulation voltage 660V |
| Rated frequency | AC50/60Hz |
| Horizontal busbar current range | 630–5000A, subject to exact construction |
| Vertical busbar current range | 800–2000A with construction-specific limits below |
| Vertical busbar construction limits | Single- or double-sided draw-out MCC:800A; movable MCC:1000A; single-sided 1000mm MCC:800–2000A |
| Horizontal busbar fault withstand | Effective short-time value 50–100kA for 1s; peak 105–250kA, as source range; exact pairing requires design confirmation |
| Vertical busbar fault withstand | Effective short-time value 60kA for 1s; peak 130–150kA; confirm exact arrangement |
| Enclosure protection | IP30 / IP40 listed. IP54 is also listed but the manufacturer explicitly does not recommend it because of severe capacity reduction. |
| Source cabinet dimensions | Original table gives 600×800 and 1000×600(1000)×2200mm using its length/width/height notation. Confirm the approved dimensional drawing rather than assuming interchangeable layouts. |
| Installation conditions | Ambient −5 to +40°C, 24-hour average ≤+35°C; altitude ≤2000m; humidity ≤50% at +40°C; installation tilt ≤5° |
| Standards in source | IEC439, GB7251 and JB/T9661 references; no independent current certification is asserted. |
Series maxima are not an independently verified complete-assembly rating. The vertical-busbar footnote is controlling for MCC configuration. IP54 is not offered as an unrestricted option because the original catalogue warns of capacity reduction. Specify project ratings, circuit schemes and exact cabinet drawings.
Typical applications
- Industrial and building low-voltage power distribution.
- Project-specific electrical switchboard replacement or new installation.
Specify your enquiry
For a focused quotation, include:
- Series, single-line diagram, main/auxiliary scheme codes, load schedule and quantity.
- Rated supply, current, fault level and duration, component specification, protection and metering.
- Cabinet layout, cable entry, IP requirement, installation environment and destination.
Download People Electric RMNS catalogue (PDF)