People Electric · Intelligent DC Air Circuit Breaker
Product overview
People Electric RDW8DC distributes power and protects compatible high-current DC networks. The2500A and4000A frames have distinct current schedules and DC voltage/series-pole combinations. The manufacturer diagrams specify the series paths; these arrangements must not be treated as an ordinary AC phase/pole connection.
Technical selection summary
| Manufacturer / series | Original People Electric RDW8DC |
|---|---|
| 2500AF rated currents | 800, 1000, 1250, 1600, 2000, 2500A |
| 4000AF rated currents | 1600, 2000, 2500, 3200, 3600, 4000A |
| 2500AF series arrangement / voltage | 2P or3P series:DC500/750V;4P series:DC1000/1500V |
| 4000AF series arrangement / voltage | 3P series:DC500/750V;4P series:DC1000/1500V |
| 2500AF Icu | 2P DC500V:50kA;2P DC750V:40kA;3P DC500V:65kA;3P DC750V:55kA;4P DC1000V:50kA;4P DC1500V:40kA |
| 4000AF Icu | 3P DC500V:120kA;3P DC750V:80kA;4P DC1000V:75kA;4P DC1500V:60kA |
| Insulation / impulse withstand | Ui1500V;Uimp12kV |
| Ics / short-time withstand | Manufacturer table lists Ics=100%Icu and Icw(1s)=100%Icu for the documented configurations |
| Controller | R:LCD enhanced type;H:LCD advanced type with communication; confirm the required protection/communication schedule |
| Main installation | Fixed or drawout; horizontal or vertical connection arrangement, subject to approved busbar drawing |
| Control supplies | AC230V,AC400V,DC110V orDC220V; these are control-circuit supplies, not the main DC operating voltage |
| Main connection diagram | 2P standard;3P A1–A4/B1–B2;4P C1–C8/D1–D2, matched to the selected series-pole arrangement |
| Operating conditions | −5 to+40°C;24-hour average≤35°C; altitude≤2000m; pollution degree3 |
| Protection enclosure | IP20 product; up toIP40 when installed in the cabinet with the specified door frame |
Frame, series-pole arrangement, voltage, current and connection drawing are linked. The2900A option is excluded because it is absent from the main frame-rating table. Specify the actual fault level, DC circuit time constant, protection coordination and busbar layout. Confirm the complete accessory/undervoltage-release and communication schedule; a control-supply selection does not define the main-circuit voltage.
Typical applications
- High-current DC distribution and line/equipment protection within the selected voltage, current, fault and DC series-connection ratings.
Specify your enquiry
For a focused quotation, include:
- Frame/series-pole/voltage arrangement, current, controller, mounting and control supply.
- Required connection diagram, busbar orientation/dimensions, prospective fault level, circuit time constant and protection settings.
- Undervoltage/accessory/interlock/communication schedule, quantity, approved cabinet drawing and destination.