People Electric · Explosion-Proof Control Box
Product overview
People Electric BXK is a configurable control-box family for assembling the required buttons, ammeters, indicators and switches in an appropriate enclosure. The manufacturer ordering diagram builds the final code from the enclosure and individual component specifications. The selectors capture project requirements; a complete factory model and bill of materials are agreed from the approved control drawing.
Technical selection summary
| Manufacturer / family | Original People Electric BXK |
|---|---|
| Supply values listed | AC 220V / AC 380V; match every installed indicator, meter and control component to its actual circuit supply |
| Catalogue rated-current entry | 10A; this is not a universal switching-capacity guarantee for every contact at every voltage or utilization category |
| Utilization categories listed | AC-3 and AC-4; actual component operational ratings, contact configuration and duty require a confirmed component schedule |
| Manufacturer Ex markings | Exdemb IIC T6 Gb and Exd IIC T6 / DIP A20 TA,T6 are printed. The ordering guidance separately references IIB and IIC components; verify the actual supplied assembly nameplate and applicable documentation. |
| Enclosure / corrosion protection | IP65; WF1 as catalogue |
| Configuration | Enclosure specification plus button, ammeter, indicator and switch specification codes; counts and component ratings are project-specific |
| Cable entry | G3/4 to G1 1/2 source entry range; cable outside diameter 9–25mm; confirm each gland, entry count, thread and cable |
| Entry orientation | D: upward; X: downward and omissible in the model explanation |
| Mounting | The manufacturer note calls for specifying suspended mounting when required; confirm final mounting arrangement and accessories |
| Component documentation | Source references separate component-code pages. Final component model, contact diagram, indicator voltage/colour and meter scale/CT ratio must be confirmed together. |
| Standards referenced | GB 3836.1, GB 3836.2, GB 3836.3 and IEC 60079; no unobserved certification is asserted |
| Reference layout | Original layout examples are retained. They do not define one standard component count or a universal interchangeable enclosure. |
This is a control assembly specified by drawing. Do not use the catalogue10A entry as an unrestricted AC-3/AC-4 contact rating or treat AC220/380V as a universal input. Confirm all contacts, actual control supplies, meter/CT details, enclosure size and hazardous-area requirements in the final factory bill of materials.
Typical applications
- Local process or equipment control using an approved combination of buttons, switches, indicators and meters.
- Project control stations requiring the actual supplied gas/dust protection marking and matching wiring accessories.
Specify your enquiry
For a focused quotation, include:
- Required button quantity, contact diagrams and operation types; indicator colours/voltages and selector functions.
- Ammeter range, CT ratio, control voltage/frequency, load category and contact duty.
- IIB/IIC requirement, ambient/site conditions, enclosure/mounting constraints, cable entries, drawings, quantity and documents.
Download People Electric BXK catalogue (PDF)