NewTrend · PV DC Isolation
Product overview
YT.2-32 is an open-type non-polar PV DC isolator for operation within an enclosure. The four-contact module supports the documented single-string and double-string wiring arrangements. Its operational voltage and current depend on wiring: up to 1200V DC at 32A for 4B/4S, and 40A only at 600V DC with the 2H parallel-contact arrangement.
Key features
- Non-polar DC isolation and control; + and − polarities may be interchanged.
- DIN-rail mounting for vertical or horizontal installation within a suitable enclosure.
- Standard rotary and lockable rotary handle views are retained in the gallery.
- Arc suppression time <3ms; flame-retardant construction.
- 15000 mechanical and 1000 electrical operating cycles.
Technical selection summary
Product identity
| Model | YT.2-32 |
|---|---|
| Construction | Open type; operation within the enclosure; DIN-rail mounting |
| Application | PV DC isolation and control in 1–20kW inverter/controller systems and residential/commercial on-grid or off-grid installations |
| Standards | IEC 60947-3; AS 60947.3:2018 |
| Utilization category | DC-PV2 |
| Poles and wiring | Four physical contacts; two-pole or four-pole DC circuit arrangements according to the documented wiring configuration |
| Rated current range | 9–40A; see the voltage/wiring correspondence below |
| Rated operational voltage Ue | 600V, 800V, 1000V, 1200V DC; 40A only at the documented 600V / 2H configuration |
Electrical performance
| Rated insulation voltage Ui | 1200V |
|---|---|
| Rated impulse withstand voltage Uimp | 8.0kV |
| Rated short-time withstand current Icw | 1kA for 1s (4 / 4S / 4B); 1.7kA for 1s (2H) |
| Rated short-circuit making capacity Icm | 1.7kA (4 / 4S / 4B); 3kA (2H) |
| Rated conditional short-circuit current | 3kA |
| Conventional enclosed thermal current Ithe | Same as rated operational current Ie |
| Rated frequency | DC |
| Polarity | Non-polar; + and − polarities may be interchanged |
| Suitability for isolation | Yes |
| Arc suppression time | <3ms |
Installation and service life
| Mechanical operating cycles | 15000 |
|---|---|
| Electrical operating cycles | 1000 |
| Switch-body protection | IP20 |
| Storage temperature | −40°C to +85°C |
| Mounting orientation | Vertical or horizontal |
| Mounting method | DIN rail |
| Suitable environment | Indoor; open switch body must be installed in a suitable enclosure |
| Pollution degree | 3 |
| Overvoltage category | II |
| Handle options | Standard rotary handle or lockable rotary handle; OFF-position locking is specified by the source |
| Standard-handle drawing dimensions | 61mm width; 95mm depth reference; 84mm overall mounting height; 75mm body/handle height reference; 62mm lower height reference |
| Lockable-handle drawing dimensions | 61mm width; 95mm depth reference; 98mm overall height reference; 65.5mm switch-body height reference |
| Source certification references | TUV / CE / CB; supplied-marking applicability to be confirmed |
Operational rating by wiring arrangement
| Wiring code | 600V DC | 800V DC | 1000V DC | 1200V DC | Poles in series | Strings |
|---|---|---|---|---|---|---|
| 4 | 32A | 13A | 9A | 9A | 2 | 2 |
| 2H | 40A | / | / | / | 2 | 1 |
| 4B | 32A | 32A | 32A | 32A | 2 | 1 |
| 4S | 32A | 32A | 32A | 32A | 4 | 1 |
Current values above are operational ratings for the specified voltage and wiring, rather than circuit-breaker trip settings. Wiring links and contact connections must follow the diagrams. The source family also lists 16A and 25A module ratings; this page uses the explicit wiring-capacity matrix shown above. Complete ordering suffix and certification applicability must be confirmed for the supplied marking.
Typical applications
Residential or commercial on-grid/off-grid PV inverter and controller DC circuits within the selected voltage and wiring rating. The open IP20 switch body is intended for indoor installation within a suitable enclosure.
Download the complete YT.2-32 family datasheet (2 pages)
The complete family PDF includes open-type and door-clutch reference material. This product page and selectable handle configurations apply to the open-type, within-enclosure version; source certification symbols are reference documentation for their stated source-product scope.
Wiring and operational-current ratings
YT.2-32 open-type module. Follow the selected 4 / 2H / 4B / 4S connection and associated voltage/current rating.
Switching configurations
YT.2-32 four-contact module. Contact numbering and connection examples correspond to the stated wiring codes.
Installation dimensions
YT.2-32 open-type standard and lockable rotary handle versions. Dimensions in mm. Door-clutch dimensions are not used for this open-type product.