UD-40/3 is a three-pole Type 2 surge protective device for 1000V photovoltaic DC circuits. Its prewired base and replaceable high-energy varistor modules provide 20kA nominal and 40kA maximum discharge current, with green/red status indication.
Key features
- Suitable for photovoltaic systems within the stated 1000V DC rating.
- Plug-in protection modules for installation and maintenance.
- High-energy varistor construction and response time ≤25ns.
- Optional floating changeover contact for remote monitoring.
Technical selection summary
Product identity
| Model | UD-40/3 |
|---|---|
| Version | 1000V DC, 3P; source UL-version construction |
| Standards referenced by source | IEC/EN 61643-31 / UL 1449 |
| Category | IEC II / EN 2 (Type 2) |
Electrical performance
| Maximum open-circuit voltage Uoc max | 1000V DC |
|---|---|
| Maximum continuous operating voltage Uc | 1000V DC |
| Nominal discharge current In (8/20μs) | 20kA |
| Maximum discharge current Imax (8/20μs) | 40kA |
| Voltage protection level Up | ≤3.8kV |
| Response time | ≤25ns |
Indication and construction
| Operating / fault indication | Green / Red |
|---|---|
| Protection construction | Prewired base with plug-in high-energy varistor modules |
| Remote signalling contact (FM) | Optional floating changeover contact |
| Remote contact maximum voltage / current | 30V DC / 1A |
| Ordering-code structure | UD – 40 / 3 1000V RC; RC denotes remote signalling contact; exact full order code to be confirmed |
Connection and installation
| Solid conductor cross-section | 4–25mm² |
|---|---|
| Flexible conductor cross-section | 4–16mm² |
| Terminal screws | M5 |
| Main-circuit tightening torque | 2.5N·m |
| Remote-contact tightening torque | 0.25N·m |
| Degree of protection | IP20 |
| Mounting | TH35-7.5 / DIN35 rail |
| Operating temperature | −40°C to +80°C |
| Relative humidity | 30–90% |
| Weight | 0.36kg |
| Outline dimensions (W × H × D) | 54 × 91.6 × 69mm |
| Drawing reference dimensions | 35mm; 46.5mm; 84.2mm; 44.5mm; 5.5mm |
Documentation scope
| Certification applicability | To be confirmed for the supplied product marking |
|---|
The product views and complete PDF show the source UL-version construction. Certification documents must match the supplied product marking. Remote-contact availability and the full ordering code require confirmation.
Typical applications
Photovoltaic DC surge protection in inverter, controller and PV DC cabinets within the stated electrical ratings.
Download the complete UD-40/3 technical datasheet (2 pages)
Principal circuit, wiring and dimensions