Product overview
Four-pole pluggable AC surge protective device, Type 1+2, with 275 V AC Uc, 7 kA Iimp, 20 kA In and 50 kA Imax.

Technical specifications
| Model | TZG40-T1T2 |
|---|---|
| Offered configuration | 4P, 275 V AC |
| SPD classification | Type 1 + Type 2 |
| Max. continuous operating voltage Uc | 275 V AC |
| Impulse current Iimp (10/350 μs) | 7 kA |
| Nominal discharge current In (8/20 μs) | 20 kA |
| Maximum discharge current Imax (8/20 μs) | 50 kA |
| Voltage protection level Up | ≤1.5 kV (shown 4P 275 V label) |
| Standard marked on product | IEC/EN 61643-11 |
| Mounting | DIN rail |
| Condition indicator | Green: normal; red: replace |
Offered configuration
This page covers the 4P 275 V AC device shown in the main photograph, with L/L/L/N and PE markings. The additional images include illustrations of other pole arrangements in the family. Confirm the exact rating and pole arrangement when ordering.
Status window and replaceable modules
The status window indicates when a module must be replaced. The module and base illustrations show the plug-in arrangement and DIN-rail mounting. Isolate the installation before inspection or replacement.