NewTrend · Y5-160
Product overview
NewTrend Y5-160 AC surge protective devices with voltage-linked Up and remote-status indication. Select the network pole arrangement and Uc.
Technical selection summary
| Parameter | Specification |
|---|---|
| Surge test references | Type1+2;Imax160kA and In100kA at8/20us;Iimp12.5kA at10/350us per original technical table |
| Uc / Up | See voltage-specific protection levels below;Uc is maximum continuous AC operating voltage, not nominal system voltage |
| Network arrangement | 3+0 or4+0 according to original supply table;3+1 is a separate circuit shown in the series drawing and is not a selectable substitution |
| Indication / alarm | Green normal,red failed;remote alarm-contact reference |
| Installation | 35mm DIN rail;IP20;terminal capacity4-35mm2 |
| Single-module outline | 90 x36 x67mm per original drawing |
| Source limitation | The original charge Q row is inconsistent between variants and is not used as a verified impulse parameter |
Surge-current ratings are waveform-specific and must not be treated as continuous load current. The series drawing includes a3+1 arrangement outside the confirmed3+0/4+0 selectors. Confirm the actual earthing system and coordinated upstream protection for the installation.
| Uc AC | Up less than |
|---|---|
| AC275V | 2.0kV |
| AC320V | 2.5kV |
| AC385V | 3.0kV |
| AC420V | 3.5kV |
| AC550V | 3.8kV |
Typical applications
- Electrical panel assembly and installation